EWPM (EN)

Extension for a KNX / EIB connection

The heat pump manager can be used as an accessory EWPM extension can be integrated into a KNX bus system.

New!
The documentation "Room temperature control Smart-RTC +" is now available for describing the room temperature, room humidity and target room temperature via the KNX extension. "

EWPM extension

Order reference

EWPM
(Discontinued at the end of 2017,
Will be replaced in the 1st quarter of 2018 by KNX WPM)

item number

356970
(Discontinued at the end of 2017,
Will be replaced in the 1st quarter of 2018 by 376350)

Operating conditions

-20 to 60 ° C
<85% RH

Cable sizing

0.2 to a maximum of 1.5 mm²; YCYM 1x2x0.8 mm²

Can be used with

WPM 2006 / R
WPM 2007 / R
WPM EconPlus / R
WPM Econ5

Available for

ETS3 / ETS4 / ETS5

Function overview

With the available as an accessory EWPM extension it is possible to integrate a Dimplex heat pump with a heat pump manager into a KNX bus system. Values for up to 110 group addresses can be sent from the heat pump manager to the KNX bus system or sent from the KNX bus system to the heat pump manager. Among other things, it is possible to read out the status, the operating data or the history in order to visualize this later on the KNX level. The operating mode, the target hot water temperature or the heating curve could also be changed.

New:
Should the function of the intelligent room temperature control Smart-RTC + be used despite the existing KNX room sensors? From the heat pump manager software WPM_L23.1, it is possible to send the room temperature, room humidity and target room temperature of up to 10 rooms with KNX room sensors from the KNX bus to the heat pump manager. Further information and descriptions are given in the chapter Room temperature control Smart-RTC + made available.

System requirement

The minimum system requirement for using the EWPM extension is a Dimplex heat pump with heat pump manager WPM 2006, WPM 2007 or WPM EconPlus from software version H_H50 and higher. For the programming a PC with ETS3, ETS4 or ETS5 software (not included), a Project file, the "KSet" programming tool and a Data point list needed.

installation

ATTENTION
Before opening the device, all circuits must be disconnected from the power supply. All electrical connection work may only be carried out by a qualified electrician or a specialist for specified activities in compliance with the installation and operating instructions.

The installation of the EWPM extension takes place on the heat pump manager in the designated slot “Serial Card / BMS Card”. The following steps are carried out:

  • De-energize the heat pump manager

  • Remove the cover of the “Serial Card / BMS Card” slot with a small screwdriver

  • Remove the cover of the “Serial Card / BMS Card” slot with a small screwdriver

  • Installation of the EWPM extension

  • Breaking out the existing cover

  • Close the opening with the cover

 

 

  • Supply the heat pump manager with voltage

Electrical connection

The EWPM extension is connected to the KNX bus using the enclosed terminal. The device is supplied with power via the KNX bus. It should be noted that a new EWPM extension does not have a physical address owns and before programmed must become.

Heat pump manager settings

Depending on the software version of the heat pump manager, the following settings must be checked and, if necessary, adjusted:

Software version

menu

Submenu

Setting value

Software version

menu

Submenu

Setting value

from WPM_H

Modem -> with the key combination «menu"+"Enter" Select

protocol

Modbus

baud rate

9600

address

001

from WPM_L

Network -> with the key «menu" Select

protocol

EIB / KNX

from WPM_L20.2

Network -> with the key «menu" Select

protocol

EIB / KNX

Address range

1..127

from WPM_L23.1

Network -> with the key «menu" Select

protocol

EIB / KNX

Address range

1..207

Import device into ETS

The EWPM extension is integrated into the ETS by importing a Project file. In the Project file the device "EWPM Plugin" is included. After the successful import, the physical address programmed and the project-related XML file Loading.

NOTE
Before a bus monitor or communication with another application can be started, communication with the device must first be established! If this is not the case, the error message appears: "Verify connection cable and restart procedure"

Import project file ETS3

The EWPM extension is imported into the ETS3 with the help of the * .pr4 project file.

  • Import project

  • Select the path to the file to be imported

  • Select the project to be imported

  • Open / manage project

  • Select and open a project

  • Device in the project

Import project file ETS4

The EWPM extension is imported into the ETS4 using the * .knxproj project file.

  • Import project

 

  • Select the path of the file to be imported

  • Choose a file

  • Imported file selected

  • Select project

  • Import selected project

  • Project imported successfully

 

Import project file ETS5 (chapter in progress)

Import project file ETS5.5.2

The EWPM extension is imported into the ETS5.5.2 with the help of the * .knxproj project file.

  • Activate the Compatibility Mode app

  • Import project

 

  • Select the path of the file to be imported

 

  • Start import

  • Project imported successfully

  • Project available in the project selection

Physical address

In order to program the physical address via the ETS, the programming button on the EWPM extension must be pressed. Then the green LED starts to light up. This goes out when the device has successfully received the physical address from the ETS.

Program communication EWPM <-> KNX bus

An XML file is required for communication between the KNX bus and the heat pump manager. This XML file must be created and adapted according to the relevant system parameters and customer requirements. The program KSet needed.

Programming tool KSet

After installing and opening KSet it is recommended to use the attached file Example.xml to open. In Example.xml the most common standard addresses are preset at the factory.

First of all, the system-specific addresses to be transmitted should be specified. The main / middle and subgroups are then created in the ETS for the addresses. Means KSet the XML file is now edited. The following figure shows the structure of the XML file in KSet shown. The individual columns are described in the following table.

split

description

split

description

Group

As in the associated ETS project, the main, middle and subgroups must be entered.

Surname

The description is optional. However, it is recommended to enter a meaningful name.

Datapoint typ*

The data point type of the desired data point must be entered.

IN / OUT*

IN: The value is sent from the KNX bus to the heat pump manager.
OUT: The value is sent from the heat pump manager to the KNX bus.

index*

The index of the desired data point must be entered.

COIL / REG*

The type of data point required must be entered.

COIL: Digital
REG: register

Conversion Rule*

If necessary, a corresponding conversion rule must be entered.

Conversion Value*

If necessary, a corresponding conversion factor must be entered.

Loading the XML file at ETS3 (in progress)

Loading the XML file with ETS4

After the user-specific XML file has been created, it must be loaded into the device for communication between the KNX bus and the heat pump manager.

  • Select device

  • "Edit" menu - select "Edit parameters"

  • Selection window appears

  • "Choose XML file" - select the XML file to be imported

  • "Download data" - Load XML file

  • "Confirmation request" - If the security question appears, this is confirmed with "Yes"

  • XML file was imported successfully, the selection window can be closed

 

 

Loading the XML file with ETS5 (in progress)

Loading the XML file with ETS5.5.2

After the user-specific XML file has been created, it must be loaded into the device for communication between the KNX bus and the heat pump manager.

  • Select device

  • Select "Parameter" - "Open product-specific parameter dialog"

  • Selection window appears - "Choose XML file"

  • Select the XML file to be imported

  • "Download data" - Load XML file

  • "Confirmation request" - If the security question appears, this is confirmed with "Yes"

  • XML file was imported successfully, the selection window can be closed

 

 

Data point list

The data point lists listed in the following tables contain the most frequently used addresses. The tables are subdivided according to the menus contained in the heat pump manager. The following examples deal with addresses that have some special features and must be explained separately.

Data points that can be written via the KNX bus are marked with "IN", those that deliver values to the KNX bus are marked with "OUT".

Operating data

Surname

Datapoint
Type

IN / OUT

index

COIL / REG

Conversion Rule

Conversion Value

DPT

R / W

Unit

WPM J / L software

WPM H software

Outside temperature (R1)

16 bit float

OUT

1

27

register

None

 

9.001

R.

° C

Return temperature (R2)

16 bit float

OUT

2

29

register

None

 

9.001

R.

° C

Set return temperature

16 bit float

OUT

53

28

register

None

 

9.001

R.

° C

Hot water temperature (R3)

16 bit float

OUT

3

30th

register

None

 

9.001

R.

° C

Flow temperature (R9)

16 bit float

OUT

5

31

register

None

 

9.001

R.

° C

Heat source inlet (R24) *

16 bit float

OUT

6th

-

register

None

 

9.001

R.

° C

Heat source outlet (R6)

16 bit float

OUT

7th

41

register

None

 

9.001

R.

° C

Temperature 2nd heating circuit (R5)

16 bit float

OUT

9

33

register

None

 

9.001

R.

° C

Temperature 3rd heating circuit (R13)

16 bit float

OUT

10

35

register

None

 

9.001

R.

° C

Room temperature 1 / RT-RTH Econ

16 bit float

OUT

11th

36

register

None

 

9.001

R.

° C

Room temperature 2

16 bit float

OUT

12th

38

register

None

 

9.001

R.

° C

Room humidity 1 / RT-RTH Econ

16 bit float

OUT

13th

37

register

None

 

9.001

R.

%

Room humidity 2

16 bit float

OUT

14th

39

register

None

 

9.001

R.

%

Passive cooling

Flow temperature (R11)

16 bit float

OUT

19th

42

register

None

 

9.001

R.

° C

Return temperature (R4)

16 bit float

OUT

20th

43

register

None

 

9.001

R.

° C

Passive / active cooling

Return temp. according to primary circuit (R24)

16 bit float

OUT

21

-

register

None

 

9.001

R.

° C

Solar

Collector sensor (R23)

16 bit float

OUT

10

-

register

None

 

9.001

R.

° C

Solar storage tank (R22)

16 bit float

OUT

23

-

register

None

 

9.001

R.

° C

ventilation

Outside air temperature

16 bit float

OUT

120

-

register

None

 

9.001

R.

° C

Supply air temperature

16 bit float

OUT

121

-

register

None

 

9.001

R.

° C

Exhaust air temperature

16 bit float

OUT

122

-

register

None

 

9.001

R.

° C

Exhaust air temperature

16 bit float

OUT

123

-

register

None

 

9.001

R.

° C

Speed of supply air fan

16 bit float

OUT

125

-

register

None

 

9.001

R.

1 / min

Exhaust fan speed

16 bit float

OUT

126

-

register

None

 

9.001

R.

1 / min

history

Surname

Datapoint
Type

IN / OUT

index

COIL / REG

Conversion Rule

Conversion Value

DPT

R / W

Unit

WPM L software address range 1..207

WPM J / L software address range 1..127

WPM H software

Compressor 1

unsigned 16 bit

OUT

72

64

register

None

 

7.007

R.

H

Compressor 2

unsigned 16 bit

OUT

73

65

register

None

 

7.007

R.

H

Primary pump / fan (M11)

unsigned 16 bit

OUT

74

66

register

None

 

7.007

R.

H

2nd heat generator (E10)

unsigned 16 bit

OUT

75

67

register

None

 

7.007

R.

H

Heating pump (M13)

unsigned 16 bit

OUT

76

68

register

None

 

7.007

R.

H

Hot water pump (M18)

unsigned 16 bit

OUT

77

69

register

None

 

7.007

R.

H

Flange heating (E9)

unsigned 16 bit

OUT

78

70

register

None

 

7.007

R.

H

Swimming pool pump (M19)

unsigned 16 bit

OUT

79

71

register

None

 

7.007

R.

H

Additional circulation pump (M16)

unsigned 16 bit

OUT

71 (from L12)

-

register

None

 

7.007

R.

H

Amount of heat* Heating 1-4

unsigned 16 bit

OUT

303

223

228

register

None

 

7.007

R.

kWh

Amount of heat* Heating 5-8

unsigned 16 bit

OUT

304

224

229

register

None

 

7.007

R.

kWh

Amount of heat* Heating 9-12

unsigned 16 bit

OUT

305

225

230

register

None

 

7.007

R.

kWh

Amount of heat* Hot water 1-4

unsigned 16 bit

OUT

306

226

231

register

None

 

7.007

R.

kWh

Amount of heat* Hot water 5-8

unsigned 16 bit

OUT

307

227

232

register

None

 

7.007

R.

kWh

Amount of heat* Hot water 9-12

unsigned 16 bit

OUT

308

228

233

register

None

 

7.007

R.

kWh

Amount of heat* Swimming pool 1-4

unsigned 16 bit

OUT

309

229

234

register

None

 

7.007

R.

kWh

Amount of heat* Swimming pool 5-8

unsigned 16 bit

OUT

310

230

235

register

None

 

7.007

R.

kWh

Amount of heat* Swimming pool 9-12

unsigned 16 bit

OUT

311

231

236

register

None

 

7.007

R.

kWh

Example of heat quantities*

The heat quantities are made up of 3 addresses. These 3 addresses must be combined with the following formula for the amount of heat.

Heat quantity heating = (14/3/225 * 100000000) + (14/3/224 * 10000) + 14/3/223

Group

Surname

Datapoint typ

IN / OUT

Address

COIL / REG

Conversion Rule

Conversion Value

Group

Surname

Datapoint typ

IN / OUT

Address

COIL / REG

Conversion Rule

Conversion Value

14/3/223

Heat quantity heating 1-4

Unsigned 16 bit

OUT

223

register

None

 

14/3/224

Heat quantity heating 5-8

Unsigned 16 bit

OUT

224

register

None

 

14/3/225

Heat quantity heating 9-12

Unsigned 16 bit

OUT

225

register

None

 

The amount of heat for "hot water" and "swimming pool" is determined according to this description. However, the corresponding address is used here.

settings

1st heating circuit

Surname

Datapoint type

IN / OUT

index

COIL / REG

Conversion Rule

Conversion Value

DPT

R / W

Range

Unit

WPM L software address range 1..207

WPM J / L software address range 1..127

WPM H software

Min

Max

Parallel shift

unsigned 16 bit

IN / OUT

243

163

129

register

None

 

7.001

R / W

0

38

K

 

0 = -19
1 = -18
2 = -17
3 = -16
4 = -15
5 = -14
6 = -13
7 = -12
8 = -11
9 = -10
10 = -9
11 = -8
12 = -7
13 = -6
14 = -5
15 = -4
16 = -3
17 = -2
18 = -1
19 = 0

20 = 1
21 = 2
22 = 3
23 = 4
24 = 5
25 = 6
26 = 7
27 = 8
28 = 9
29 = 10
30 = 11
31 = 12
32 = 13
33 = 14
34 = 15
35 = 16
36 = 17
37 = 18
38 = 19
 

 

Room temperature

unsigned 16 bit

IN / OUT

46

21

register

None

 

7.001

R / W

15.0

30.0

° C

Fixed setpoint temperature

unsigned 16 bit

IN / OUT

244

164

130

register

None

 

7.001

R / W

18th

60

° C

Heating curve end point

unsigned 16 bit

IN / OUT

245

165

142

register

None

 

7.001

R / W

20th

70

° C

Hysteresis

unsigned 16 bit

IN

47

22nd

register

Divide

10

7.001

W.

0.5

5.0

K

Hysteresis

unsigned 16 bit

OUT

47

22nd

register

Multiply

10

7.001

R.

0.5

5.0

K

Target temp. dyn. cooling

unsigned 16 bit

IN / OUT

-

170

151

register

None

 

7.001

R / W

10

35

° C

Target temp. dyn. cooling
at 15 ° C AT

unsigned 16 bit

IN / OUT

250

-

register

None

 

7.001

R / W

10

35

° C

Target temp. dyn. cooling
at 35 ° C AT

unsigned 16 bit

IN / OUT

341

-

register

None

 

7.001

R / W

10

35

° C

2nd / 3rd heating circuit

In order to be able to make changes to the 2nd or 3rd heating circuit, the changeover must take place via an address. After switching over this address, it is possible to change parameters in the desired heating circuit without any problems.

Surname

Datapoint type

IN / OUT

index

COIL / REG

Conversion Rule

Conversion Value

DPT

R / W

Range

Unit

WPM L software address range 1..207

WPM H / J / L software address range 1..127

Min

Max

Select heating circuit 2/3

Unsigned 16 bit

IN / OUT

289

209

register

None

 

7.001

R / W

2

3

no

 

2 = 2nd heating circuit
3 = 3rd heating circuit

Heating curve end point

Unsigned 16 bit

IN / OUT

291

211

register

None

 

7.001

R / W

20th

70

° C

Fixed value temperature

Unsigned 16 bit

IN / OUT

292

212

register

None

 

7.001

R / W

20th

60

° C

Parallel shift

Unsigned 16 bit

IN / OUT

293

213

register

None

 

7.001

R / W

0

38

K

 

0 = -19
1 = -18
2 = -17
3 = -16
4 = -15
5 = -14
6 = -13
7 = -12
8 = -11
9 = -10
10 = -9
11 = -8
12 = -7
13 = -6
14 = -5
15 = -4
16 = -3
17 = -2
18 = -1
19 = 0

20 = 1
21 = 2
22 = 3
23 = 4
24 = 5
25 = 6
26 = 7
27 = 8
28 = 9
29 = 10
30 = 11
31 = 12
32 = 13
33 = 14
34 = 15
35 = 16
36 = 17
37 = 18
38 = 19
 

 

Mixer runtime

Unsigned 16 bit

IN / OUT

294

214

register

None

 

7.001

R / W

1

6th

min

Mixer hysteresis

Unsigned 16 bit

IN

93

register

Divide

10

7.001

W.

0.5

2.0

K

Mixer hysteresis

Unsigned 16 bit

OUT

93

register

Multiply

10

7.001

R.

0.5

2.0

K

Maximum temperature

Unsigned 16 bit

IN / OUT

295

215

register

None

 

7.001

R / W

30th

70

° C

Cooling set room temperature

Unsigned 16 bit

IN / OUT

296

216

register

None

 

7.001

R / W

0

30th

° C

 

0 = 15.0
1 = 15.5
2 = 16.0
3 = 16.5
4 = 17.0
5 = 17.5
6 = 18.0
7 = 18.5
8 = 19.0
9 = 19.5
10 = 20.0
11 = 20.5
12 = 21.0
13 = 21.5
14 = 22.0
15 = 22.5

16 = 23.0
17 = 23.5
18 = 24.0
19 = 24.5
20 = 25.0
21 = 25.5
22 = 26.0
23 = 26.5
24 = 27.0
25 = 27.5
26 = 28.0
27 = 28.5
28 = 29.0
29 = 29.5
30 = 30.0
 

° C

 

operation mode

Surname

Datapoint type

IN / OUT

index

COIL / REG

Conversion Rule

Conversion Value

DPT

R / W

Range

Unit

WPM L software address range 1..207

WPM J / L software address range 1..127

WPM H software

Min

Max

operation mode

Unsigned 16 bit

IN / OUT

222

142

134

register

None

 

7.001

R / W

0

5

no

 

0 = summer
1 = auto
2 = vacation
3 = party
4 = 2nd heat generator
5 = cooling

Number of party hours

Unsigned 16 bit

IN / OUT

223

143

135

register

None

 

7.001

R / W

0

72

hour

Number of vacation days

Unsigned 16 bit

IN / OUT

224

144

136

register

None

 

7.001

R / W

0

150

day

ventilation

 

stages

Unsigned 16 bit

IN / OUT

241

161

-

register

None

 

7.001

R / W

0

5

no

 

0 = off
1 = automatic
2 = level 1
3 = level 2
4 = level 3
5 = intermittent ventilation

Time value burst ventilation

Unsigned 16 bit

IN / OUT

127

-

register

None

 

7.001

R / W

15th

90

min

Example of operating mode

When editing, it is recommended to always create IN before OUT for writable data points.

Group

Surname

Datapoint typ

IN / OUT

Address

COIL / REG

Conversion Rule

Conversion Value

Group

Surname

Datapoint typ

IN / OUT

Address

COIL / REG

Conversion Rule

Conversion Value

14/2/142

Change operating mode

Unsigned 16 bit

IN

142

register

None

 

14/3/142

Show operating mode

Unsigned 16 bit

OUT

142

register

None

 

Hot water

Surname

Datapoint type

IN / OUT

index

COIL / REG

Conversion Rule

Conversion Value

DPT

R / W

Range

Unit

WPM L software address range 1..207

WPM J / L software address range 1..127

WPM H software

Min

Max

Hysteresis

Unsigned 16 bit

IN / OUT

252

172

131

register

None

 

7.001

R / W

2

15th

K

Target temperature

Unsigned 16 bit

IN / OUT

254

174

149

register

None

 

7.001

R / W

30th

85

° C

swimming pool

Surname

Datapoint type

IN / OUT

index

COIL / REG

Conversion Rule

Conversion Value

DPT

R / W

Range

Unit

WPM L software address range 1..207

WPM J / L software address range 1..127

WPM H software

Min

Max

Hysteresis

Unsigned 16 bit

IN / OUT

256

176

-

register

None

 

7.001

R / W

1

20th

K

Target temperature

Unsigned 16 bit

IN / OUT

258

178

-

register

None

 

7.001

R / W

5

60

° C

2. Heat generator

Surname

Datapoint type

IN / OUT

index

COIL / REG

Conversion Rule

Conversion Value

DPT

R / W

Range

Unit

WPM L software address range 1..207

WPM J / L software address range 1..127

WPM H software

Min.

Max.

Mixer hysteresis

Unsigned 16 bit

IN / OUT

48

20th

register

Divide

10

7.001

R / W

0.5

2.0

K

Mixer hysteresis

Unsigned 16 bit

IN / OUT

48

20th

register

Multiply

10

7.001

 

0.5

2.0

K

Limit temperature parallel

Signed 8 bit

IN / OUT

227

147

19th

register

None

 

6,010

R / W

-25

35

° C

Mixer runtime

Unsigned 16 bit

IN / OUT

228

148

37

register

None

 

7.001

R / W

30th

85

min

Selection of time functions

Access to the time functions, e.g. for blocking, lowering / increasing values or times, is achieved by switching over the address 192 (Modbus IP 5065).

Lowering / raising

Surname

Datapoint type

IN / OUT

index

COIL / REG

Conversion Rule

Conversion Value

DPT

R / W

Range

Unit

WPM L software address range 1..207

WPM H / J / L software address range 1..127

Min.

Max.

1st heating circuit

Subsidence

Unsigned 16 bit

IN / OUT

272

192

register

None

 

7.001

R / W

1

1

no

Raising

Unsigned 16 bit

IN / OUT

272

192

register

None

 

7.001

R / W

2

2

no

2nd heating circuit

Subsidence

Unsigned 16 bit

IN / OUT

272

192

register

None

 

7.001

R / W

3

3

no

Raising

Unsigned 16 bit

IN / OUT

272

192

register

None

 

7.001

R / W

4th

4th

no

3rd heating circuit

Subsidence

Unsigned 16 bit

IN / OUT

272

192

register

None

 

7.001

R / W

5

5

no

Raising

Unsigned 16 bit

IN / OUT

272

192

register

None

 

7.001

R / W

6th

6th

no

Time function

Start hour 1

Unsigned 16 bit

IN / OUT

273

193

register

None

 

7.001

R / W

0

23

hour

Start minute 1

Unsigned 16 bit

IN / OUT

274

194

register

None

 

7.001

R / W

0

59

min

End of hour 1

Unsigned 16 bit

IN / OUT

275

195

register

None

 

7.001

R / W

0

23

hour

End of minute 1

Unsigned 16 bit

IN / OUT

276

196

register

None

 

7.001

R / W

0

59

min

Start hour 2

Unsigned 16 bit

IN / OUT

277

197

register

None

 

7.001

R / W

0

23

hour

Start minute 2

Unsigned 16 bit

IN / OUT

278

198

register

None

 

7.001

R / W

0

59

min

End of lesson 2

Unsigned 16 bit

IN / OUT

279

199

register

None

 

7.001

R / W

0

23

hour

End of minute 2

Unsigned 16 bit

IN / OUT

280

200

register

None

 

7.001

R / W

0

59

min

Sunday

Unsigned 16 bit

IN / OUT

281

201

register

None

 

7.001

R / W

0

3

no

Monday

Unsigned 16 bit

IN / OUT

282

202

register

None

 

7.001

R / W

0

3

no

Tuesday

Unsigned 16 bit

IN / OUT

283

203

register

None

 

7.001

R / W

0

3

no

Wednesday

Unsigned 16 bit

IN / OUT

284

204

register

None

 

7.001

R / W

0

3

no

Thursday

Unsigned 16 bit

IN / OUT

285

205

register

None

 

7.001

R / W

0

3

no

Friday

Unsigned 16 bit

IN / OUT

286

206

register

None

 

7.001

R / W

0

3

no

Saturday

Unsigned 16 bit

IN / OUT

287

207

register

None

 

7.001

R / W

0

3

no

 

0 = yes
1 = no
2 = time 1
3 = time 2

Reduction / increase value

Unsigned 16 bit

IN / OUT

288

208

register

None

 

7.001

R / W

0

19th

K

Active time 1

Boolean

OUT

125

Coil

None

 

1,001

R.

0

1

no

Active time 2

Boolean

OUT

126

Coil

None

 

1,001

R.

0

1

no

Hot water lock

Surname

Datapoint type

IN / OUT

index

COIL / REG

Conversion Rule

Conversion Value

DPT

R / W

Range

Unit

WPM L software address range 1..207

WPM H / J / L software address range 1..127

Min.

Max.

Hot water lock

Unsigned 16 bit

IN / OUT

272

192

register

None

 

7.001

R / W

7th

7th

no

Time function

Start hour 1

Unsigned 16 bit

IN / OUT

273

193

register

None

 

7.001

R / W

0

23

hour

Start minute 1

Unsigned 16 bit

IN / OUT

274

194

register

None

 

7.001

R / W

0

59

min

End of hour 1

Unsigned 16 bit

IN / OUT

275

195

register

None

 

7.001

R / W

0

23

hour

End of minute 1

Unsigned 16 bit

IN / OUT

276

196

register

None

 

7.001

R / W

0

59

min

Start hour 2

Unsigned 16 bit

IN / OUT

277

197

register

None

 

7.001

R / W

0

23

hour

Start minute 2

Unsigned 16 bit

IN / OUT

278

198

register

None

 

7.001

R / W

0

59

min

End of lesson 2

Unsigned 16 bit

IN / OUT

279

199

register

None

 

7.001

R / W

0

23

hour

End of minute 2

Unsigned 16 bit

IN / OUT

280

200

register

None

 

7.001

R / W

0

59

min

Sunday

Unsigned 16 bit

IN / OUT

281

201

register

None

 

7.001

R / W

0

3

no

Monday

Unsigned 16 bit

IN / OUT

282

202

register

None

 

7.001

R / W

0

3

no

Tuesday

Unsigned 16 bit

IN / OUT

283

203

register

None

 

7.001

R / W

0

3

no

Wednesday

Unsigned 16 bit

IN / OUT

284

204

register

None

 

7.001

R / W

0

3

no

Thursday

Unsigned 16 bit

IN / OUT

285

205

register

None

 

7.001

R / W

0

3

no

Friday

Unsigned 16 bit

IN / OUT

286

206

register

None

 

7.001

R / W

0

3

no

Saturday

Unsigned 16 bit

IN / OUT

287

207

register

None

 

7.001

R / W

0

3

no

 

0 = yes
1 = no
2 = time 1
3 = time 2

Active time 1

Boolean

OUT

125

Coil

None

 

1,001

R.

0

1

no

Active time 2

Boolean

OUT

126

Coil

None

 

1,001

R.

0

1

no

Thermal disinfection

Surname

Datapoint type

IN / OUT

index

COIL / REG

Conversion Rule

Conversion Value

DPT

R / W

Range

Unit

WPM L software address range 1..207

WPM H / J / L software address range 1..127

Min.

Max.

Thermal disinfection

Unsigned 16 bit

IN / OUT

272

192

register

None

 

7.001

R / W

8th

8th

no

Time function

Start hour

Unsigned 16 bit

IN / OUT

273

193

register

None

 

7.001

R / W

0

23

hour

Start minute

Unsigned 16 bit

IN / OUT

274

194

register

None

 

7.001

R / W

0

59

min

Sunday

Unsigned 16 bit

IN / OUT

281

201

register

None

 

7.001

R / W

0

1

no

Monday

Unsigned 16 bit

IN / OUT

282

202

register

None

 

7.001

R / W

0

1

no

Tuesday

Unsigned 16 bit

IN / OUT

283

203

register

None

 

7.001

R / W

0

1

no

Wednesday

Unsigned 16 bit

IN / OUT

284

204

register

None

 

7.001

R / W

0

1

no

Thursday

Unsigned 16 bit

IN / OUT

285

205

register

None

 

7.001

R / W

0

1

no

Friday

Unsigned 16 bit

IN / OUT

286

206

register

None

 

7.001

R / W

0

1

no

Saturday

Unsigned 16 bit

IN / OUT

287

207

register

None

 

7.001

R / W

0

1

no

 

0 = yes
1 = no

temperature

Unsigned 16 bit

IN / OUT

288

208

register

None

 

7.001

R / W

60

85

° C

active

Boolean

OUT

125

Coil

None

 

1,001

R.

0

1

no

DHW circulation pump

Surname

Datapoint type

IN / OUT

index

COIL / REG

Conversion Rule

Conversion Value

DPT

R / W

Range

Unit

WPM L software address range 1..207

WPM H / J / L software address range 1..127

Min.

Max.

Circulation pump

Unsigned 16 bit

IN / OUT

272

192

register

None

 

7.001

R / W

12th

12th

no

Time function

Start hour 1

Unsigned 16 bit

IN / OUT

273

193

register

None

 

7.001

R / W

0

23

hour

Start minute 1

Unsigned 16 bit

IN / OUT

274

194

register

None

 

7.001

R / W

0

59

min

End of hour 1

Unsigned 16 bit

IN / OUT

275

195

register

None

 

7.001

R / W

0

23

hour

End of minute 1

Unsigned 16 bit

IN / OUT

276

196

register

None

 

7.001

R / W

0

59

min

Start hour 2

Unsigned 16 bit

IN / OUT

277

197

register

None

 

7.001

R / W

0

23

hour

Start minute 2

Unsigned 16 bit

IN / OUT

278

198

register

None

 

7.001

R / W

0

59

min

End of lesson 2

Unsigned 16 bit

IN / OUT

279

199

register

None

 

7.001

R / W

0

23

hour

End of minute 2

Unsigned 16 bit

IN / OUT

280

200

register

None

 

7.001

R / W

0

59

min

Sunday

Unsigned 16 bit

IN / OUT

281

201

register

None

 

7.001

R / W

0

3

no

Monday

Unsigned 16 bit

IN / OUT

282

202

register

None

 

7.001

R / W

0

3

no

Tuesday

Unsigned 16 bit

IN / OUT

283

203

register

None

 

7.001

R / W

0

3

no

Wednesday

Unsigned 16 bit

IN / OUT

284

204

register

None

 

7.001

R / W

0

3

no

Thursday

Unsigned 16 bit

IN / OUT

285

205

register

None

 

7.001

R / W

0

3

no

Friday

Unsigned 16 bit

IN / OUT

286

206

register

None

 

7.001

R / W

0

3

no

Saturday

Unsigned 16 bit

IN / OUT

287

207

register

None

 

7.001

R / W

0

3

no

 

0 = yes
1 = no
2 = time 1
3 = time 2

Active time 1

Boolean

OUT

125

Coil

None

 

1,001

R.

0

1

no

Active time 2

Boolean

OUT

126

Coil

None

 

1,001

R.

0

1

no

Display ads

Surname

Datapoint type

IN / OUT

index

COIL / REG

Conversion Rule

Conversion Value

DPT

R / W

Range

Unit

WPM L software

WPM J software

WPM H software

Min.

Max.

Status reports

Unsigned 16 bit

OUT

103

43

14th

register

None

 

7.001

R.

0

30th

no

Heat pump lock

Unsigned 16 bit

OUT

104

59

94

register

None

 

7.001

R.

1

42

no

Fault messages

Unsigned 16 bit

OUT

105

42

13th

register

None

 

7.001

R.

1

31

no

Sensors

Unsigned 16 bit

OUT

106

-

-

register

None

 

7.001

R.

1

27

no

Status reports

Value

Description

L software

H / J software

0

the end

the end

1

the end

Heat pump on heating

2

Heat

Heat pump on heating

3

swimming pool

Heat pump A swimming pool

4th

Hot water

Heat pump One hot water

5

Cool

Heat pump One heating + 2nd heat generator

6th

 

Heat pump A swimming pool + 2nd heat generator

7th

 

Heat pump One hot water + 2nd heat generator

8th

 

Primary pump supply

9

 

Heating rinse

10

Defrost

Lock (see value for lock J software)

11th

Flow monitoring

Lower limit of use

12th

 

Low pressure limit

13th

 

Low pressure shutdown

14th

 

High pressure protection

15th

 

Switching cycle lock

16

 

Minimum service life

17th

 

Network load

18th

 

Flow monitoring

19th

 

2. Heat generator

20th

 

Low pressure brine

21

 

Heat pump on defrost

22nd

 

Upper limit of use

23

 

External lock

24

Operating mode switchover delay

Operating mode cooling

25th

 

Frost protection cold

26th

 

Lead limit

27

 

Dew point monitor

28

 

dew point

29

 

Passive cooling

30th

Lock (see value for lock L software)

 

Lock



Value

Description

L software

J software

H software

0

 

 

 

1

 

Application limit HT

Outside temperature

2

Volume flow

Application limit WP

Bivalent alternative

3

 

Regenerative

Bivalent regenerative

4th

 

 

Rewind

5

Function control

Hot water reheating

Hot water

6th

Application limit HT

System control

System control

7th

System control

EVU lock

EVU lock

8th

Cooling switchover delay

 

 

9

Pump feed

High pressure

 

10

Minimum service life

Low pressure

 

11th

Network load

Flow

 

12th

Switching cycle lock

Soft starter

 

13th

Hot water reheating

 

 

14th

Regenerative

 

 

15th

EVU lock

 

 

16

Soft starter

 

 

17th

Flow

 

 

18th

Application limit heat pump

 

 

19th

High pressure

 

 

20th

Low pressure

 

 

21

Application limit heat source

 

 

23

System limit

 

 

24

Load primary circuit

 

 

25th

External lock

 

 

33

EvD initialization

 

 

34

2. Heat generator released

 

 

35

Fault (see value for fault messages)

 

 

36

 

Pump feed

 

37

 

Minimum service life

 

38

 

Network load

 

39

 

Switching cycle lock

 

40

 

Application limit heat source

 

41

 

External lock

 

42

 

2. Heat generator

 

43

 

Fault (see value for fault messages)

 

Fault messages



Value

Description

L software

H / J software

0

no mistake

no mistake

1

Error N17.1

 

2

Error N17.2

 

3

Error N17.3

Load compressor

4th

Error N17.4

Coding

5

 

Low pressure

6th

Electronic Ex valve

Antifreeze

7th

 

Outside sensor short circuit or break

8th

 

Return sensor short circuit or break

9

 

Hot water sensor short circuit or break

10

WPIO

Frost protection sensor short circuit or break

11th

 

2nd heating circuit sensor short circuit or break

12th

Inverter

Freeze protection sensor short circuit or break

13th

WQIF

Low pressure brine

14th

 

Motor protection primary

15th

Sensors

Flow

16

Low pressure brine

Hot water

17th

 

High pressure

19th

 ! Primary circuit

Hot gas thermostat

20th

 ! Defrost

Application limit cooling

21

 ! Low pressure brine

 

22nd

 ! Hot water

 

23

 ! Load compressor

Temperature difference

24

 ! Coding

 

25th

 ! Low pressure

 

26th

 ! Frost protection

 

28

 ! High pressure

 

29

 ! Temperature difference

 

30th

 ! Hot gas thermostat

 

31

 ! Flow

 

Sensors

Value

Description

L software

1

Outside sensor (R1)

2

Return sensor (R2)

3

Hot water sensor (R3)

4th

Coding (R7)

5

Flow sensor (R9)

6th

2nd heating circuit sensor (R5)

7th

3rd heating circuit sensor (R13)

8th

Regenerative sensor (R13)

9

Room sensor 1

10

Room sensor 2

11th

Heat source outlet sensor (R6)

12th

Heat source inlet sensor (R24) *

14th

Collector sensor (R23)

15th

Low pressure sensor (R25)

16

High pressure sensor (R26)

17th

Room humidity 1

18th

Room humidity 2

19th

Frost protection cold sensor

20th

Hot gas

21

Return sensor (R2.1)

22nd

Swimming pool sensor (R20)

23

Flow sensor cooling passive (R11)

24

Return flow sensor cooling passive (R4)

26th

Solar cylinder sensor (R22)

28

Demand sensor for heating (R2.2)

29

RTM Econ

30th

Demand sensor cooling (R39)

Entrances

Surname

Datapoint
Type

IN / OUT

index

COIL / REG

Conversion Rule

Conversion Value

DPT

R / W

Unit

WPM J / L software

WPM H software

Hot water thermostat (ID1)

Boolean

OUT

3

57

Coil

None

 

1,001

R.

no

Swimming pool thermostat (ID2)

Boolean

OUT

4th

58

Coil

None

 

1,001

R.

no

EVU lock (ID3)

Boolean

OUT

5

56

Coil

None

 

1,001

R.

no

External lock (ID4)

Boolean

OUT

6th

63

Coil

None

 

1,001

R.

no

Outputs

Surname

Datapoint
Type

IN / OUT

index

COIL / REG

Conversion Rule

Conversion Value

DPT

R / W

Unit

WPM J / L software

WPM H software

Compressor 1

Boolean

OUT

41

80

Coil

None

 

1,001

R.

no

Compressor 2

Boolean

OUT

42

81

Coil

None

 

1,001

R.

no

Primary pump (M11) / fan (M2)

Boolean

OUT

43

82

Coil

None

 

1,001

R.

no

2nd heat generator (E10)

Boolean

OUT

44

83

Coil

None

 

1,001

R.

no

Heating pump (M13)

Boolean

OUT

45

84

Coil

None

 

1,001

R.

no

Hot water pump (M18)

Boolean

OUT

46

85

Coil

None

 

1,001

R.

no

Mixer (M21) open

Boolean

OUT

47

86

Coil

None

 

1,001

R.

no

Mixer (M21) CLOSED

Boolean

OUT

48

87

Coil

None

 

1,001

R.

no

Additional circulation pump (M16)

Boolean

OUT

49

88

Coil

None

 

1,001

R.

no

Flange heating (E9)

Boolean

OUT

50

89

Coil

None

 

1,001

R.

no

Heating pump (M15)

Boolean

OUT

51

90

Coil

None

 

1,001

R.

no

Mixer (M22) open

Boolean

OUT

52

91

Coil

None

 

1,001

R.

no

Mixer (M22) closed

Boolean

OUT

53

92

Coil

None

 

1,001

R.

no

Swimming pool pump (M19)

Boolean

OUT

56

95

Coil

None

 

1,001

R.

no

Collective fault message (H5)

Boolean

OUT

57

-

Coil

None

 

1,001

R.

no

Heating pump (M14)

Boolean

OUT

59

94

Coil

None

 

1,001

R.

no

Cooling pump (M17)

Boolean

OUT

60

99

Coil

None

 

1,001

R.

no

Heating pump (M20)

Boolean

OUT

61

-

Coil

None

 

1,001

R.

no

Changeover room thermostats
Heating / cooling (N9)

Boolean

OUT

66

96

Coil

None

 

1,001

R.

no

Primary pump cooling (M12)

Boolean

OUT

68

98

Coil

None

 

1,001

R.

no

Solar pump (M23)

Boolean

OUT

71

-

Coil

None

 

1,001

R.

nss

Time alignment

Using the time synchronization, it is possible to write the current date and time via the interface. So that the change is accepted by the heat pump manager, the value 1 must be written to the associated "set register" immediately after the time has been written. Only then will the change be applied. The value of the "set register" is automatically reset to the value 0 after writing.

Surname

Datapoint type

IN / OUT

index

COIL / REG

Conversion Rule

Conversion Value

DPT

R / W

Range

Unit

WPM L software address range 1..207

WPM J / L software address range 1..127

Min.

Max.

hour

Unsigned 16 bit

IN / OUT

213

133

register

None

 

7.001

R / W

0

23

hour

set hour

Boolean

IN

102

Coil

None

 

1,001

W.

 

no

minute

Unsigned 16 bit

IN / OUT

214

134

register

None

 

7.001

R / W

0

59

min

set minute

Boolean

IN

103

Coil

None

 

1,001

W.

 

no

month

Unsigned 16 bit

IN / OUT

215

135

register

None

 

7.001

R / W

1

12th

month

set month

Boolean

IN

105

Coil

None

 

1,001

W.

 

no

weekday

Unsigned 16 bit

IN / OUT

216

136

register

None

 

7.001

R / W

1

7th

wday

 

1 = Monday
2 = Tuesday
3 = Wednesday
4 = Thursday
5 = Friday
6 = Saturday
7 = Sunday

set day of the week

Boolean

IN

107

Coil

None

 

1,001

W.

 

no

Day

Unsigned 16 bit

IN / OUT

217

137

register

None

 

7.001

R / W

1

31

day

set day

Boolean

IN

104

Coil

None

 

1,001

W.

 

no

year

Unsigned 16 bit

IN / OUT

218

138

register

None

 

7.001

R / W

0

99

year

set year

Boolean

IN

106

Coil

None

 

1,001

W.

 

no

Function descriptions

In this chapter, some functional descriptions, their implementation and recommendations are collected and explained.

Room temperature control Smart-RTC +

From software version WPM_L23.1 it is possible to use the function of the intelligent room temperature control Smart-RTC + via the BMS interface with the KNX protocol available on the heat pump manager.

The values of the room temperature, the room humidity (for cooling) and the target room temperature of a maximum of 10 rooms must be sent to the heat pump manager via the KNX bus. The heat pump manager uses these values to calculate the maximum system temperature required for heating and the minimum possible system temperature for silent cooling, taking the dew point into account. At the end of this functional description there is a Example project for the ETS4 / 5 made available. This project folder also contains the XML file related to this project.

Necessary settings on the heat pump manager

To use the BMS interface for the intelligent room temperature control Smart-RTC +, additional settings must be made or adjusted on the heat pump manager.

Software version

Pre-configuration menu

Submenu

Setting value

Software version

Pre-configuration menu

Submenu

Setting value

from WPM_L23.1

with the key combination «menu"+"ESC" Select

1st heating circuit

Heating or heating / silent cooling

1st heating / cooling circuit heating control via

Room temperature

1. Heating / cooling circuit heating room control

BMS

1. Heating / cooling circuit cooling room control

BMS

1. Heating / cooling circuit Number of room controls

01-10

When using an additional 2nd heating or heating / cooling circuit, the settings must be made in the same way as for the 1st heating circuit.

Software version

Pre-configuration menu

Submenu

Setting value

Software version

Pre-configuration menu

Submenu

Setting value

from WPM_L23.1

with the key combination «menu"+"ESC" Select

2nd heating circuit

Heating or heating / silent cooling

2nd heating / cooling circuit heating control via

Room temperature

2. Heating / cooling circuit heating room control

BMS

2. Heating / cooling circuit cooling room control

BMS

2nd heating / cooling circuit number of room controls

01-10

Room control data points

Since only a limited number of addresses are available, the time function switch from Chapter is required to write the values for the rooms "Selection of time functions" utilized. The addresses 50 - 59 for the 1st heating / cooling circuit and 60 - 69 for the 2nd heating / cooling circuit are available for access. A switchover takes place via address 272.

Surname

Datapoint
Type

IN / OUT

Address

COIL / REG

Conversion Rule

Conversion Value

DPT

R / W

Range

Unit

Min.

Max.

Room addresses 1st heating / cooling circuit

Unsigned 16 bit

IN / OUT

272

register

None

 

7.001

R / W

50

59

no

Room addresses 2nd heating / cooling circuit

Unsigned 16 bit

IN / OUT

272

register

None

 

7.001

R / W

60

69

no

Room temperature

Unsigned 16 bit

IN / OUT

11th

register

None

 

7.001

R / W

100

500

0.1 ° C

Room humidity

Unsigned 16 bit

IN / OUT

13th

register

None

 

7.001

R / W

200

900

0.1%

Target room temperature

Unsigned 16 bit

IN / OUT

288

register

None

 

7.001

R / W

100

300

0.1 ° C

Room clearance

Unsigned 16 bit

IN / OUT

371

register

None

 

7.001

R / W

1

3

no

 

1 = heating (cooling blocked)
3 = heating and cooling

Example for writing the room values

The following table relates to the group addresses in the sample project.

Surname

e.g. Group Address

Surname

e.g. Group Address

Read number of rooms

14/5/1 (sensor)

Switch room address 50 - 59

14/5/2 (actuator)

Write actual room temperature RIT addr. 50 - 59

14/5/4 (actuator)

Write actual room humidity RIF addr. 50 - 59

14/5/6 (actuator)

Write room target temperature RST addr. 50 - 59

14/5/8 (actuator)

Write room release RFG addr. 50 - 59

14/5/10 (actuator)

The address (14/5/2) is switched over to transfer the room values. The following description is intended to represent one possibility of such an implementation. The room values are written to the heat pump manager every 1 minute per room. With 10 rooms, this means a maximum processing time of 10 minutes. This lead time is not a problem with the small changes in room values and will not limit comfort.

Module 1 - Switching the room addresses

In module 1, a counter is first created which counts up by +1 every minute (pulse for minute). The count starts at 50 and ends with the number of room controllers set (sensor 14/5/1). After the number of set room controllers has been reached, counting starts again at address 50. This count value is written to actuator 14/5/2 every minute. At the same time, marker 1 (AI memory flags 1) is also filled with the counter value. Flag 3 (AI memory flags 3) triggered with the minute pulse. Both flags are required in module 2. The input M with the constant 0 means that the counter starts again at 50 when the number of set room controllers is reached and does not stop when the set room controllers are reached.

Module 2 - Delayed writing of the room values

After switching the room addresses with module 1, the writing of the values via actuators 14/5/4 (room temperature), 14/5/6 (room humidity), 14/5/8 (target room temperature) and 14 / is delayed by 3 seconds. 5/10 (room clearance). For this, marker 1 (AI memory flags 1) and marker 3 (AI memory flags 3) from step 1 are required. First, a delayed pulse by 3 seconds (delayed time 3 sec.) Is filled via marker 3 (AI memory flags 3). The delayed pulse triggers the analogue memory, which is already filled with marker 1 (AI memory flags 1) count value from module 1. If the delayed pulse is triggered, the value is written from the analogue memory to marker 2 (AI memory flags 2). The value in marker 2 (AI memory flags 2) is still required in module 3.

Module 3 - Compare the room address to be written

The marker 2 (AI memory flags 2) from module 2 contains the current value of the room address that is to be written. So that the correct trigger of the room address is triggered, the room address from marker 2 (AI memory flags 2) must be compared. The marker 2 (AI memory flags 2) is compared with the constant 50 (Constant 50). If the value is the same, another marker 50 (AI memory flags 50) is set. The marker 50 (AI memory flags 50) is required in module 4 and triggers the trigger there.

Module 4 - Writing the room values to the buffer

Module 4 is explained using the example of the target room temperature for room address 50 (Room-set-temperature 50). First, the target room temperature (Room-set-temperature 50) is multiplied by the factor x10. This is necessary because only integers (*) are written. The result is written to an analogue memory. If the marker 50 (AI memory flags 50) is triggered from step 3, the number in the analog memory (analogue memory) is written to the marker RST 50 (AI memory flags RST 50), which in turn simultaneously drives the actuator 14/5 / 8 triggers for the target room temperature.

Module 5 - Writing the room values to the heat pump manager

Module 5 shows how the room values are triggered in the actuator. It stands
RIT => actual room temperature
RIF => actual room humidity
RST => target room temperature
RFG => room release.

summary

The modules 1 - 5 serve as an example and represent a possibility for the implementation of the description of the room values. The process was deliberately divided into individual modules so that the process can be explained as simply as possible. The modules shown can also be combined, structured differently, or other paths can be selected.

Sample project for Smart-RTC + room temperature control

Attention only for

Example project from L23.1 software *

Content of the sample projects

German

English

ETS 5.5.2

Smart-RTC + v01 for ETS5.5.2 with XML file

Smart-RTC + v01 for ETS5.5.2 with XML file

  • Writing of room and target room temperature, room humidity, room release

  • Display of outside, return, hot water, flow, return setpoint and hot water setpoint temperature

  • Change the target hot water temperature and operating mode

  • History of compressor, primary, heating, hot water and swimming pool pump, 2nd heat generator, flange heating

  • Outputs from the compressor, primary, heating, hot water, swimming pool and additional circulation pump, 2nd heat generator, flange heating

  • Messages of operating mode, status, locks and faults

ETS 5

Smart-RTC + v01 for ETS5 with XML file

Smart-RTC + v01 for ETS5 with XML file

ETS 4

Smart-RTC + v01 for ETS4 with XML file

Smart-RTC + v01 for ETS4 with XML file

Smart-Grid / SG Ready

The use of photovoltaic electricity ultimately represents a load-variable tariff, since the heat pump can be operated with inexpensive electricity with photovoltaic yield. In this case, a digital input for "green" electricity can be connected on the heat pump manager. In this operating state, the heat pump runs in increased mode for room heating (return target temperature + increase value) and hot water preparation (maximum temperature hot water). The possibility of release via the available interfaces is also given from heat pump manager software version L20.2. The wiring of the digital input is then not required to enable the function.

Operating states

Condition

Address

Description

action

3

4th

Red

0

1

In this state, the heat pump runs in reduced mode for space heating and hot water generation.

  • the adjustable reduction value of the respective heating circuit applies to room heating

  • The adjustable minimum hot water temperature applies to hot water generation

yellow

0

0

In this state, the heat pump runs in the set normal mode.

 

green

1

0

In this state, the heat pump runs in increased mode for space heating and hot water preparation.

  • the adjustable increase value of the respective heating circuit applies to room heating

  • The adjustable maximum hot water temperature applies to hot water generation *

  • In the case of bivalent-renewable systems, the heat pump is not blocked; the heat pump receives priority 1 in this state

Implementation on the heat pump manager

 

Address

Datapoint type

IN / OUT

Conversion Rule

Conversion Value

DPT

R / W

Unit

Surname

WPM software L

Operating status "green"

3

Boolean

IN / OUT

None

 

1,001

R / W

no

Operating status "red"

4th

Boolean

IN / OUT

None

 

1,001

R / W

no

Downloads

Sample projects

Attention only for

Example project for H software *

Example project for J / L software *

Content of the sample projects

German

English

German

English

ETS 5.5.2

Project v01 for ETS5.5.2 with XML file

 

  • Display of outside, return, hot water, flow, room, return setpoint and hot water setpoint temperature

  • Changing the target room temperature, target hot water temperature, heating curve and operating mode

  • History of compressor, primary, heating, hot water and swimming pool pump, 2nd heat generator, flange heating

  • Outputs from the compressor, primary, heating, hot water, swimming pool and additional circulation pump, 2nd heat generator, flange heating

  • Messages of operating mode, status and fault

ETS 5

ETS 4

Project h03 for ETS4 with XML file

Project v03 for ETS4 with XML file

 

Project v03 for ETS4 with XML file

ETS 3

Project h03 for ETS3 with XML file

Project h03 for ETS3 with XML file

Project v03 for ETS3 with XML file

Project v03 for ETS3 with XML file

Caution! Only project file from ETS 5.5.2

Caution! Only project file for ETS 5

Caution! Only project file for ETS 4

Caution! Only project file for ETS 3

Download KSet

Meaning of the LED

LED

 

meaning

solution

LED

 

meaning

solution

Red

Shines

No communication between the EWPM extension and the heat pump manager

  • Address not correct

  • Incorrect baud rate

  • Protocol incorrect

 

Flashes

Communication error between the EWPM extension and the heat pump manager

  • Address not correct

  • BIOS on the heat pump manager does not support the use of the EWPM extension

green

Shines

The programming button for the assignment of the physical address has been pressed. The EWPM extension waits for the physical address to be assigned by the ETS.

 

 

Flashes quickly

  • the XML file was not loaded

  • one quick flash

the physical address was accepted after pressing the programming button

 

 

Flashes slowly

Configuration running: ETS loads the XML file

 

Green red

both light up

No power supply via the KNX bus

Check the

  • Power supply of the KNX bus

  • electrical connections

  • Polarity of the connections "+/-"

EWPM extension

1

Programming button

2

LED red

3

LED green

Contact

For further questions, information and suggestions, please send an email to:

ferndiagnose@gdts.one

with information from:

  • Heat pump designation

  • Software status heat pump manager

  • Designation of the ETS version

  • ETS export of the associated group addresses