BACnet/IP - Wärme- und Energiemengen
# keyname | object-name | object-type | object-instance | present-value-default | hi-limit | low-limit | state-text-reference | unit-code | ReadWriteCommandable |
---|---|---|---|---|---|---|---|---|---|
Integer Variable 95 | Heizen 1-4 | 2 | 200095 | 0.0 | 0.0 | 0.0 |
| 19 | R |
Integer Variable 96 | Heizen 5-8 | 2 | 200096 | 0.0 | 0.0 | 0.0 |
| 19 | R |
Integer Variable 97 | Heizen 9-12 | 2 | 200097 | 0.0 | 0.0 | 0.0 |
| 19 | R |
Integer Variable 98 | Warmwasser 1-4 | 2 | 200098 | 0.0 | 0.0 | 0.0 |
| 19 | R |
Integer Variable 99 | Warmwasser 5-8 | 2 | 200099 | 0.0 | 0.0 | 0.0 |
| 19 | R |
Integer Variable 100 | Warmwasser 9-12 | 2 | 200100 | 0.0 | 0.0 | 0.0 |
| 19 | R |
Integer Variable 101 | Schwimmbad 1-4 | 2 | 200101 | 0.0 | 0.0 | 0.0 |
| 19 | R |
Integer Variable 102 | Schwimmbad 5-8 | 2 | 200102 | 0.0 | 0.0 | 0.0 |
| 19 | R |
Integer Variable 103 | Schwimmbad 9-12 | 2 | 200103 | 0.0 | 0.0 | 0.0 |
| 19 | R |
Integer Variable 126 | Umweltenergie 1-4 | 2 | 200126 | 0.0 | 0.0 | 0.0 |
| 19 | R |
Integer Variable 127 | Umweltenergie 5-8 | 2 | 200127 | 0.0 | 0.0 | 0.0 |
| 19 | R |
Integer Variable 128 | Umweltenergie 9-12 | 2 | 200128 | 0.0 | 0.0 | 0.0 |
| 19 | R |
*HINWEIS
Eine Wärmemenge kann nur bei Wärmepumpen mit integriertem Wärmemengenzähler ausgelesen werden!
Beispiel Wärmemengen*
Die Wärmemengen setzen sich aus 3 Indizes zusammen. Diese 3 Indizes müssen mit folgender Formel zur Wärmemenge zusammengesetzt werden.
Wärmemenge Heizen = (Wärmemenge Heizen 9-12 * 100000000) + (Wärmemenge Heizen 5-8 * 10000) + Wärmemenge Heizen 1-4 |
Entsprechend dieser Beschreibung wird die Wärmemenge für "Warmwasser" und "Schwimmbad" ermittelt. Jedoch wird hierbei der entsprechende Datenpunkt genutzt.