BACnet/IP - Betriebsdaten
# keyname | object-name | object-type | object-instance | present-value-default | hi-limit | low-limit | state-text-reference | unit-code | ReadWriteCommandable |
---|---|---|---|---|---|---|---|---|---|
Analog Variable 1 | Außentemperatur (R1) | 2 | 100001 | 0.0 | 0.0 | 0.0 |
| 62 | R |
Analog Variable 2 | Ruecklauftemperatur (R2) | 2 | 100002 | 0.0 | 0.0 | 0.0 |
| 62 | R |
Analog Variable 3 | Warmwassertemperatur (R3) | 2 | 100003 | 0.0 | 0.0 | 0.0 |
| 62 | R |
Analog Variable 5 | Vorlauftemperatur (R9) | 2 | 100005 | 0.0 | 0.0 | 0.0 |
| 62 | R |
Analog Variable 6 | Waermequelleneintritt (R24)* | 2 | 100006 | 0.0 | 0.0 | 0.0 |
| 62 | R |
Analog Variable 7 | Waermequellenaustritt (R6) | 2 | 100007 | 0.0 | 0.0 | 0.0 |
| 95 | R |
Analog Variable 8 | Hochdruck | 2 | 100008 | 0.0 | 0.0 | 0.0 |
| 55 | R |
Analog Variable 9 | Temperatur 2. Heizkreis (R5) | 2 | 100009 | 0.0 | 0.0 | 0.0 |
| 62 | R |
Analog Variable 10 | Temperatur 3. Heizkreis | 2 | 100010 | 0.0 | 0.0 | 0.0 |
| 62 | R |
Analog Variable 11 | Raumtemperatur 1 / RT-RTH Econ | 2 | 1000011 | 0.0 | 0.0 | 0.0 |
| 62 | R |
Analog Variable 12 | Raumtemperatur 2 | 2 | 100012 | 0.0 | 0.0 | 0.0 |
| 62 | R |
Analog Variable 13 | Raumfeuchte 1 / RT-RTH Econ | 2 | 100013 | 0.0 | 0.0 | 0.0 |
| 29 | R |
Analog Variable 14 | Raumfeuchte 2 | 2 | 100014 | 0.0 | 0.0 | 0.0 |
| 29 | R |
Analog Variable 46 | Raumtemperatur 1. Heizkreis | 2 | 1000046 | 20.0 | 30.0 | 15.0 |
| 62 | W |
Analog Variable 53 | Ruecklaufsolltemperatur (Hz/Khl) | 2 | 100053 | 0.0 | 0.0 | 0.0 |
| 62 | R |
Analog Variable 54 | Solltemperatur 2. Heizkreis | 2 | 100054 | 0.0 | 0.0 | 0.0 |
| 62 | R |
Analog Variable 55 | Solltemperatur 3. Heizkreis | 2 | 100055 | 0.0 | 0.0 | 0.0 |
| 62 | R |
Analog Variable 56 | Minimale Temperatur 2. Heizkreis | 2 | 100056 | 0.0 | 0.0 | 0.0 |
| 62 | R |
Analog Variable 57 | Minimale Temperatur 2. Heizkreis | 2 | 100057 | 0.0 | 0.0 | 0.0 |
| 62 | R |
Analog Variable 58 | Aktuelle Warmwasser-Solltemperatur | 2 | 100058 | 0.0 | 0.0 | 0.0 |
| 62 | R |
Analog Variable 60 | Leistungsstufe Heizen | 2 | 100060 | 0.0 | 0.0 | 0.0 |
| 95 | R |
Analog Variable 61 | Leistungsstufe Kuehlen | 2 | 100061 | 0.0 | 0.0 | 0.0 |
| 95 | R |
Analog Variable 101 | Niederdruck | 2 | 100101 | 0.0 | 0.0 | 0.0 |
| 55 | R |
Passiv Kühlen | |||||||||
Analog Variable 19 | Vorlauftemperatur (R11) Passiv Kuehlen | 2 | 100019 | 0.0 | 0.0 | 0.0 |
| 62 | R |
Analog Variable 20 | Ruecklauftemperatur (R4) Passiv Kuehlen | 2 | 100020 | 0.0 | 0.0 | 0.0 |
| 62 | R |
Passiv/Aktiv Kühlen | |||||||||
Analog Variable 21 | Ruecklauftemperatur gemeinsamer Primaerkreis (R24) | 2 | 100021 | 0.0 | 0.0 | 0.0 |
| 62 | R |
Lüftung | |||||||||
Analog Variable 120 | Außenlufttemperatur | 2 | 100120 | 0.0 | 0.0 | 0.0 |
| 62 | R |
Analog Variable 121 | Zulufttemperatur | 2 | 100121 | 0.0 | 0.0 | 0.0 |
| 62 | R |
Analog Variable 122 | Ablufttemperatur | 2 | 100122 | 0.0 | 0.0 | 0.0 |
| 62 | R |
Analog Variable 123 | Fortlufttemperatur | 2 | 100123 | 0.0 | 0.0 | 0.0 |
| 62 | R |
Analog Variable 125 | Drehzahl Zuluftventilator | 2 | 100125 | 0.0 | 0.0 | 0.0 |
| 104 | R |
Analog Variable 126 | Drehzahl Abluftventilator | 2 | 100126 | 0.0 | 0.0 | 0.0 |
| 104 | R |
*HINWEIS
Der Wärmequelleneintritt ist nur bei Wärmepumpen mit elektronischem Expansionsventil vorhanden.