Address | Datapoint Typ | COIL/REG | R/W | Unit | ||
Name | WPM-Software J/L/M | WPM-Software H | ||||
---|---|---|---|---|---|---|
Außentemperatur (R1) | 1 | 27 | int16 | Register | R | 0.1 °C |
Temperatur Ruecklauf (R2) | 2 | 29 | int16 | Register | R | 0.1 °C |
Temperatur Rücklaufsoll | 53 | 28 | int16 | Register | R | 0.1 °C |
Temperatur Warmwasser (R3) | 3 | 30 | int16 | Register | R | 0.1 °C |
Temperatur Warmwassersoll | 58 | 40 | int16 | Register | R | 0.1 °C |
Temperatur Vorlauf (R9) | 5 | 31 | int16 | Register | R | 0.1 °C |
Temperatur Wärmequelleneintritt (R24)* | 6 | - | int16 | Register | R | 0.1 °C |
Temperatur Wärmequellenaustritt (R6) | 7 | 41 | int16 | Register | R | 0.1 °C |
Solltemperatur 2.Heizkreis | 54 | 32 | int16 | Register | R | 0.1 °C |
Temperatur 2.Heizkreis (R5) | 9 | 33 | int16 | Register | R | 0.1 °C |
Solltemperatur 3.Heizkreis | 55 | 34 | int16 | Register | R | 0.1 °C |
Temperatur 3.Heizkreis (R13) | 10 | 35 | int16 | Register | R | 0.1 °C |
Raumtemperatur 1 / RT-RTH Econ | 11 | 36 | int16 | Register | R | 0.1 °C |
Raumtemperatur 2 | 12 | 38 | int16 | Register | R | 0.1 °C |
Raumfeuchte 1 / RT-RTH Econ | 13 | 37 | int16 | Register | R | 0.1 r.F. |
Raumfeuchte 2 | 14 | 39 | int16 | Register | R | 0.1 r.F. |
Passiv Kühlen | ||||||
Vorlauftemperatur (R11) | 19 | 42 | int16 | Register | R | 0.1 °C |
Rücklauftemperatur (R4) | 20 | 43 | int16 | Register | R | 0.1 °C |
Passiv/Aktiv Kühlen | ||||||
Rücklauftemp. gem. Primärkreis (R24) | 21 | - | int16 | Register | R | 0.1 °C |
Solar | ||||||
Kollektorfühler (R23) | 10 | - | int16 | Register | R | 0.1 °C |
Solarspeicher (R22) | 23 | - | int16 | Register | R | 0.1 °C |
Lüftung | ||||||
Außenlufttemperatur | 120 | - | int16 | Register | R | 0.1 °C |
Zulufttemperatur | 121 | - | int16 | Register | R | 0.1 °C |
Ablufttemperatur | 122 | - | int16 | Register | R | 0.1 °C |
Fortlufttemperatur | 123 | - | int16 | Register | R | 0.1 °C |
Drehzahl Zuluftventilator | 125 | - | int16 | Register | R | 1/min |
Drehzahl Abluftventilator | 126 | - | int16 | Register | R | 1/min |
*HINWEIS
Der Wärmequelleneintritt ist nur bei Wärmepumpen mit elektronischem Expansionsventil vorhanden.