Versions Compared

Key

  • This line was added.
  • This line was removed.
  • Formatting was changed.
Address

Register

Datapoint Typ

COIL/REG

R/W

Unit

Name

WPM-Software J/L/M

WPM-Software H

Außentemperatur (R1)

127

int16

Register

R

0.1 °C

Temperatur Ruecklauf (R2)

229

int16

Register

R

0.1 °C

Temperatur Rücklaufsoll

5328

int16

Register

R

0.1 °C

Temperatur Warmwasser (R3)

3

30

int16

Register

R

0.1 °C

Temperatur Warmwassersoll

5840

int16

Register

R

0.1 °C

Temperatur Vorlauf (R9)

531

int16

Register

R

0.1 °C

Temperatur Wärmequelleneintritt (R24)*

6-

int16

Register

R

0.1 °C

Temperatur Wärmequellenaustritt (R6)

741

int16

Register

R

0.1 °C

Solltemperatur 2.Heizkreis

5432

int16

Register

R

0.1 °C

Temperatur 2.Heizkreis (R5)

933

int16

Register

R

0.1 °C

Solltemperatur 3.Heizkreis

5534

int16

Register

R

0.1 °C

Temperatur 3.Heizkreis (R13)

10

35

int16

Register

R

0.1 °C

Raumtemperatur 1 / RT-RTH Econ

1136

int16

Register

R

0.1 °C

Raumtemperatur 2

1238

int16

Register

R

0.1 °C

Raumfeuchte 1 / RT-RTH Econ

1337

int16

Register

R

0.1 r.F.

Raumfeuchte 2

1439

int16

Register

R

0.1 r.F.

Passiv Kühlen

Vorlauftemperatur (R11)

1942

int16

Register

R

0.1 °C

Rücklauftemperatur (R4)

2043

int16

Register

R

0.1 °C

Passiv/Aktiv Kühlen

Rücklauftemp. gem. Primärkreis (R24)

21-

int16

Register

R

0.1 °C

Solar

Kollektorfühler (R23)

10-

int16

Register

R

0.1 °C

Solarspeicher (R22)

23-

int16

Register

R

0.1 °C

Lüftung

Außenlufttemperatur

120-

int16

Register

R

0.1 °C

Zulufttemperatur

121-

int16

Register

R

0.1 °C

Ablufttemperatur

122-

int16

Register

R

0.1 °C

Fortlufttemperatur

123-

int16

Register

R

0.1 °C

Drehzahl Zuluftventilator

125-

int16

Register

R

1/min

Drehzahl Abluftventilator

126-

int16

Register

R

1/min

Info

*HINWEIS
Der Wärmequelleneintritt ist nur bei Wärmepumpen mit elektronischem Expansionsventil vorhanden.