Address | Datapoint Typ | COIL/REG | R/W | Unit | Name | WPM-Software J/L/||
---|---|---|---|---|---|---|---|
Address | Datapoint Typ | COIL/REG | R/W | Unit | |||
Name | WPM-Software J/L/M | WPM-Software H | |||||
Außentemperatur (R1) | 1 | 27 | Float 16 bitint16 | Register | R | 0.1 °C | |
Temperatur Ruecklauf (R2) | 2 | 29 | Float 16 bit | int16 | Register | R | 0.1 °C |
Temperatur Rücklaufsoll | 53 | 28 | Float 16 bitint16 | Register | R | 0.1 °C | |
Temperatur Warmwasser (R3) | 3 | 30 | Float 16 bitint16 | Register | R | 0.1 °C | |
Temperatur Warmwassersoll | 58 | 40 | Float 16 bitint16 | Register | R | 0.1 °C | |
Temperatur Vorlauf (R9) | 5 | 31 | Float 16 bitint16 | Register | R | 0.1 °C | |
Temperatur Wärmequelleneintritt (R24)* | 6 | - | Float 16 bitint16 | Register | R | 0.1 °C | |
Temperatur Wärmequellenaustritt (R6) | 7 | 41 | Float 16 bitint16 | Register | R | 0.1 °C | |
Solltemperatur 2.Heizkreis | 54 | 32 | Float 16 bitint16 | Register | R | 0.1 °C | |
Temperatur 2.Heizkreis (R5) | 9 | 33 | Float 16 bitint16 | Register | R | 0.1 °C | |
Solltemperatur 3.Heizkreis | 55 | 34 | Float 16 bitint16 | Register | R | 0.1 °C | |
Temperatur 3.Heizkreis (R13) | 10 | 35 | Float 16 bitint16 | Register | R | 0.1 °C | |
Raumtemperatur 1 / RT-RTH Econ | 11 | 36 | Float 16 bitint16 | Register | R | 0.1 °C | |
Raumtemperatur 2 | 12 | 38 | Float 16 bitint16 | Register | R | 0.1 °C | |
Raumfeuchte 1 / RT-RTH Econ | 13 | 37 | Float 16 bitint16 | Register | R°C | 0.1 r.F. | |
Raumfeuchte 2 | 14 | 39 | Float 16 bitint16 | Register | R°C | 0.1 r.F. | |
Passiv Kühlen | |||||||
Vorlauftemperatur (R11) | 19 | 42 | Float 16 bitint16 | Register | R | 0.1 °C | |
Rücklauftemperatur (R4) | 20 | 43 | Float 16 bitint16 | Register | R | 0.1 °C | |
Passiv/Aktiv Kühlen | |||||||
Rücklauftemp. gem. Primärkreis (R24) | 21 | - | Float 16 bitint16 | Register | R | 0.1 °C | |
Solar | |||||||
Kollektorfühler (R23) | 10 | - | Float 16 bitint16 | Register | R | °C | |
Solarspeicher (R22) | 23 | - | Float 16 bitint16 | Register | R°C | 0.1 °CC | |
Lüftung | |||||||
Außenlufttemperatur | 120 | - | Float 16 bitint16 | Register | R | 0.1 °C | |
Zulufttemperatur | 121 | - | Float 16 bitint16 | Register | R | 0.1 °C | |
Ablufttemperatur | 122 | - | Float 16 bitint16 | Register | R | 0.1 °C | |
Fortlufttemperatur | 123 | - | Float 16 bitint16 | Register | R | 0.1 °C | |
Drehzahl Zuluftventilator | 125 | - | Float 16 bitint16 | Register | R | 1/min | |
Drehzahl Abluftventilator | 126 | - | Float 16 bitint16 | Register | R | 1/min |
Info |
---|
*HINWEIS |
6.
...
3 Einstellungen
6.3.1 1.Heizkreis
Address | Datapoint Typ | COIL/REG | R/W | Range | Unit | |||
Name | WPM-Software J/L/M | WPM-Software H |
Min |
Max |
Parallelverschiebung |
uint16
Register
R
hour
Verdichter 2
73
5036 | 5002 | uint16 | Register | R |
hour
Primärpumpe / Ventilator (M11)
74
66
uint16
Register
R
hour
2.Wärmeerzeuger (E10)
75
67
uint16
Register
R
hour
Heizungspumpe (M13)
76
68
uint16
Register
R
hour
Warmwasserpumpe (M18)
77
69
uint16
Register
R
hour
Flanschheizung (E9)
78
70
uint16
Register
R
hour
Schwimmbadpumpe (M19)
79
71
uint16
Register
R
hour
Zusatzumwälzpumpe (M16)
71
ab L12
-
uint16
Register
R
hour
Wärmemenge* Heizen 1-4
5096
5101
uint16
Register
R
kWh
Wärmemenge* Heizen 5-8
5097
5102
uint16
Register
R
kWh
Wärmemenge* Heizen 9-12
5098
5103
uint16
Register
R
kWh
Wärmemenge* Warmwasser 1-4
5099
5104
uint16
Register
R
kWh
Wärmemenge* Warmwasser 5-8
5100
5105
uint16
Register
R
kWh
Wärmemenge* Warmwasser 9-12
5101
5106
uint16
Register
R
kWh
Wärmemenge* Schwimmbad 1-4
5102
5107
uint16
Register
R
kWh
Wärmemenge* Schwimmbad 5-8
5103
5108
uint16
Register
R
kWh
Wärmemenge* Schwimmbad 9-12
5104
5109
uint16
Register
R
kWh
Info |
---|
*HINWEIS |
6.2.1 Beispiel Wärmemengen*
Die Wärmemengen setzen sich aus 3 Indizes zusammen. Diese 3 Indizes müssen mit folgender Formel zur Wärmemenge zusammengesetzt werden.
Wärmemenge Heizen = (Wärmemenge Heizen 9-12 * 100000000) + (Wärmemenge Heizen 5-8 * 10000) + Wärmemenge Heizen 1-4
Entsprechend dieser Beschreibung wird die Wärmemenge für "Warmwasser" und "Schwimmbad" ermittelt. Jedoch wird hierbei der entsprechende Datenpunkt genutzt.
6.3 Einstellungen
6.3.1 1.Heizkreis
...
Address
...
Datapoint Typ
...
COIL/REG
...
R/W
...
Range
...
Unit
...
Name
...
WPM-Software J/L/M
...
WPM-Software H
...
Min
...
Max
...
Parallelverschiebung
...
5036
...
5002
...
uint16
...
Register
...
R/W
...
0
...
38
...
0: -19
1: -18
2: -17
3: -16
4: -15
5: -14
6: -13
7: -12
8: -11
9: -10
10: -9
11: -8
12: -7
13: -6
14: -5
15: -4
16: -3
17: -2
18: -1
19: 0
...
20: 1
21: 2
22: 3
23: 4
24: 5
25: 6
26: 7
27: 8
28: 9
29: 10
30: 11
31: 12
32: 13
33: 14
34: 15
35: 16
36: 17
37: 18
38: 19
...
Raumtemperatur
...
46
...
21
...
uint16
...
Register
...
R/W
...
15.0
...
30.0
...
°C
...
Festwertsolltemperatur
...
5037
...
5003
...
uint16
...
Register
...
R/W
...
18
...
60
...
°C
...
Heizkurvenendpunkt
...
5038
...
5015
...
uint16
...
Register
...
R/W
...
20
...
70
...
°C
...
Hysterese
...
47
...
22
...
uint16
...
Register
...
R/W
...
0.5
...
5.0
...
K
...
Solltemp. dyn. Kühlung (bis L22.9)
...
5043
...
5024
...
uint16
...
Register
...
R/W
...
10
...
35
...
°C
...
Solltemp. dyn. Kühlung bei 15°C AT (ab L22.9)
...
5043
...
-
...
uint16
...
Register
...
R/W
...
10
...
35
...
°C
...
Solltemp. dyn. Kühlung bei 35°C AT (ab L22.9)
...
5134
...
-
...
uint16
...
Register
...
R/W
...
10
...
35
...
°C
6.3.2 2./3.Heizkreis
Um Änderungen am 2. oder 3.Heizkreis vornehmen zu können, muss die Umschaltung über eine Adresse erfolgen. Nach Umschaltung dieser Adresse ist eine problemlose Parameteränderung im gewünschten Heizkreis möglich.
Info |
---|
*HINWEIS |
...
Address
...
Datapoint Typ
...
COIL/REG
...
R/W
...
Range
...
Unit
...
Name
...
Min.
...
Max.
...
Auswahl Heizkreis 2
...
5082
...
uint16
...
Register
...
R/W
...
2
...
2
...
Auswahl Heizkreis 3
...
5082
...
uint16
...
Register
...
R/W
...
3
...
3
...
2: 2.Heizkreis
3: 3.Heizkreis
...
Heizkurvenendpunkt
...
5084
...
uint16
...
Register
...
R/W
...
20
...
70
...
°C
...
Festwertemperatur
...
5085
...
uint16
...
Register
...
R/W
...
20
...
60
...
°C
...
Parallelverschiebung
...
5086
...
uint16t
...
Register
...
R/W
...
0
...
38
...
0: -19
1: -18
2: -17
3: -16
4: -15
5: -14
6: -13
7: -12
8: -11
9: -10
10: -9
11: -8
12: -7
13: -6
14: -5
15: -4
16: -3
17: -2
18: -1
19: 0
...
20: 1
21: 2
22: 3
23: 4
24: 5
25: 6
26: 7
27: 8
28: 9
29: 10
30: 11
31: 12
32: 13
33: 14
34: 15
35: 16
36: 17
37: 18
38: 19
...
Mischerlaufzeit
...
5087
...
uint16
...
Register
...
R/W
...
1
...
6
...
Min
...
Mischerhysterese
...
93
...
uint16
...
Register
...
R/W
...
0.5
...
2.0
...
K
...
Maximale Temperatur
...
5088
...
uint16
...
Register
...
R/W
...
30
...
70
...
°C
...
Kühlung Raumsolltemperatur
...
5089
...
uint16
...
Register
...
R/W
...
0
...
30
...
0: 15.0
1: 15.5
2: 16.0
3: 16.5
4: 17.0
5: 17.5
6: 18.0
7: 18.5
8: 19.0
9: 19.5
10: 20.0
11: 20.5
12: 21.0
13: 21.5
14: 22.0
15: 22.5
...
16: 23.0
17: 23.5
18: 24.0
19: 24.5
20: 25.0
21: 25.5
22: 26.0
23: 26.5
24: 27.0
25: 27.5
26: 28.0
27: 28.5
28: 29.0
29: 29.5
30: 30.0
...
°C
6.3.3 Modus
/W | 0 | 38 | ||||||
0: -19 | 20: 1 | |||||||
Raumtemperatur | 46 | 21 | uint16 | Register | R/W | 15.0 | 30.0 | °C |
Festwertsolltemperatur | 5037 | 5003 | uint16 | Register | R/W | 18 | 60 | °C |
Heizkurvenendpunkt | 5038 | 5015 | uint16 | Register | R/W | 20 | 70 | °C |
Hysterese | 47 | 22 | uint16 | Register | R/W | 0.5 | 5.0 | K |
Solltemp. dyn. Kühlung (bis L22.9) | 5043 | 5024 | uint16 | Register | R/W | 10 | 35 | °C |
Solltemp. dyn. Kühlung bei 15°C AT (ab L22.9) | 5043 | - | uint16 | Register | R/W | 10 | 35 | °C |
Solltemp. dyn. Kühlung bei 35°C AT (ab L22.9) | 5134 | - | uint16 | Register | R/W | 10 | 35 | °C |
6.3.2 2./3.Heizkreis
Um Änderungen am 2. oder 3.Heizkreis vornehmen zu können, muss die Umschaltung über eine Adresse erfolgen. Nach Umschaltung dieser Adresse ist eine problemlose Parameteränderung im gewünschten Heizkreis möglich.
Info |
---|
*HINWEIS |
Address | Datapoint Typ | COIL/REG | R/W | Range | Unit | ||
Name |
---|
WPM-Software J/L/M
WPM-Software H
Min
Max
Betriebsmodus
5015
Min. | Max. | ||||||
---|---|---|---|---|---|---|---|
Auswahl Heizkreis 2 | 5082 | uint16 | Register | R/W | 2 | 2 | |
Auswahl Heizkreis 3 | 5082 | uint16 | Register | R/W |
3 |
3 |
2: |
2.Heizkreis |
2: Urlaub
3: Party
4: 2.Wärmeerzeuger
5: Kühlen
Anzahl Partystunden
5016
3: 3.Heizkreis | |||||||
Heizkurvenendpunkt | 5084 | uint16 | Register | R/W | 20 | 70 | °C |
Festwertemperatur | 5085 | uint16 | Register | R/W |
20 |
60 |
°C |
Parallelverschiebung |
5086 |
5009
uint16t | Register | R |
0
150
day
Lüftung
Stufen
5034
-
uint16
Register
R/W
0
5
Zeitwert Stoßlüften
127
-
uint16
Register
R/W
15
90
Info |
---|
HINWEIS |
6.3.4 Warmwasser
Address
Datapoint Typ
COIL/REG
R/W
Range
Unit
Name
WPM-Software J/L/M
WPM-Software H
Min
Max
Hysterese
5045
/W | 0 | 38 | |||||
0: -19 | 20: 1 | ||||||
Mischerlaufzeit | 5087 | uint16 | Register | R/W |
1 |
6 |
Min |
Mischerhysterese |
5047
93 | uint16 | Register | R/W |
0. |
5 | 2.0 |
K |
°C
Solltemperatur Minimal
5145
Maximale Temperatur | 5088 | uint16 | Register | R/W |
30 |
70 | °C |
Kühlung Raumsolltemperatur |
5089 |
-
uint16 | Register | R/W |
Soll.
85
°C
6.3.5 Schwimmbad
Address
Datapoint Typ
COIL/REG
R/W
Range
Unit
Name
WPM-Software J/L/M
WPM-Software H
Min
Max
Hysterese
5049
-
uint16
Register
R/W
1
20
K
Solltemperatur
5051
-
uint16
Register
R/W
5
0 | 30 | ||||||
0: 15.0 | 16: 23.0 | °C |
6.3.6 2.Wärmeerzeuger
...
Ein Zugriff auf die Zeitfunktionen für z.B. Sperren, Absenk-/ Anhebwerte oder Zeiten erfolgt über das Umschalten der Adresse 5065.
Info |
---|
HINWEIS |
...
Value | Description |
---|---|
L/M-Software | |
1 | Außenfühler (R1) |
2 | Rücklauffühler (R2) |
3 | Warmwasserfühler (R3) |
4 | Codierung (R7) |
5 | Vorlauffühler (R9) |
6 | 2.Heizkreisfühler (R5) |
7 | 3.Heizkreisfühler (R13) |
8 | Regenerativfühler (R13) |
9 | Raumfühler 1 |
10 | Raumfühler 2 |
11 | Fühler Wärmequellenaustritt (R6) |
12 | Fühler Wärmequelleneintritt (R24)* |
14 | Kollektorfühler (R23) |
15 | Niederdrucksensor (R25) |
16 | Hochdrucksensor (R26) |
17 | Raumfeuchte 1 |
18 | Raumfeuchte 2 |
19 | Fühler Frostschutz-Kälte |
20 | Heißgas |
21 | Rücklauffühler (R2.1) |
22 | Schwimmbadfühler (R20) |
23 | Vorlauffühler Kühlen Passiv (R11) |
24 | Rücklauffühler Kühlen Passiv (R4) |
26 | Fühler Solarspeicher (R22) |
28 | Anforderungsfühler Heizen (R2.2) |
29 | RTM Econ |
30 | Anforderungsfühler Kühlen (R39) |
Info |
---|
*HINWEIS |
...
Address | Datapoint Typ | COIL/REG | R/W | ||
---|---|---|---|---|---|
Software Wärmepumpenmanager | WPM-Software J/L/M | WPM-Software H | |||
Adressbereich | 1 … 127 / 1 … 207 | - | |||
Bezeichnung | |||||
Warmwassertermostat | 3 | 57 | boolean | Coil | R |
Schwimmbadthermostat | 4 | 58 | boolean | Coil | R |
EVU-Sperre | 5 | 56 | boolean | Coil | R |
Sperre Extern | 6 | 63 | boolean | Coil | R |
Info |
---|
HINWEIS |
...
Address | Datapoint Typ | COIL/REG | R/W | ||
---|---|---|---|---|---|
Name | WPM-Software J/L | WPM-Software H | |||
Verdichter 1 | 41 | 80 | Boolean | Coil | R |
Verdichter 2 | 42 | 81 | Boolean | Coil | R |
Primärpumpe (M11) / Ventilator (M2) | 43 | 82 | Boolean | Coil | R |
2.Wärmeerzeuger (E10) | 44 | 83 | Boolean | Coil | R |
Heizungspumpe (M13) | 45 | 84 | Boolean | Coil | R |
Warmwasserpumpe (M18) | 46 | 85 | Boolean | Coil | R |
Mischer (M21) Auf | 47 | 86 | Boolean | Coil | R |
Mischer (M21) ZU | 48 | 87 | Boolean | Coil | R |
Zusatzumwälzpumpe (M16) | 49 | 88 | Boolean | Coil | R |
Flanschheizung (E9) | 50 | 89 | Boolean | Coil | R |
Heizungspumpe (M15) | 51 | 90 | Boolean | Coil | R |
Mischer (M22) Auf | 52 | 91 | Boolean | Coil | R |
Mischer (M22) Zu | 53 | 92 | Boolean | Coil | R |
Schwimmbadpumpe (M19) | 56 | 95 | Boolean | Coil | R |
Sammelstörmeldung (H5) | 57 | - | Boolean | Coil | R |
Heizungspumpe (M14) | 59 | 94 | Boolean | Coil | R |
Kühlpumpe (M17) | 60 | 99 | Boolean | Coil | R |
Heizungspumpe (M20) | 61 | - | Boolean | Coil | R |
Umschaltung Raumthermostate Heizen/Kühlen (N9) | 66 | 96 | Boolean | Coil | R |
Primärpumpe Kühlen (M12) | 68 | 98 | Boolean | Coil | R |
Solarpumpe (M23) | 71 | - | Boolean | Coil | R |
Info |
---|
HINWEIS |
...
Address | Datapoint Typ | COIL/REG | R/W | Range | Unit | ||
---|---|---|---|---|---|---|---|
Name | Min. | Max. | |||||
Stunde | 5006 | uint16 | Register | R/W | 0 | 23 | hour |
set Stunde | 102 | boolean | Coil | W | |||
Minute | 5007 | uint16 | Register | R/W | 0 | 59 | min |
set Minute | 103 | boolean | Coil | W | |||
Monat | 5008 | uint16 | Register | R/W | 1 | 12 | month |
set Monat | 105 | boolean | Coil | W | |||
Wochentag | 5009 | uint16 | Register | R/W | 1 | 7 | |
1:Montag | |||||||
set Wochentag | 107 | boolean | Coil | W | |||
Tag | 5010 | uint16 | Register | R/W | 1 | 31 | day |
set Tag | 104 | boolean | Coil | W | |||
Jahr | 5011 | uint16 | Register | R/W | 0 | 99 | year |
set Jahr | 106 | boolean | Coil | W |
Info |
---|
*HINWEIS |
...
Parameter | Einstellung | Einstellwert | |
---|---|---|---|
1./2./3.Kreis | |||
1./2./3.Kreis | Welche Regelungsmöglichkeit soll für den 1./2./3.Kreis genutzt werden? | Raumtemperatur | |
1./2./3.Kreis | Welche Hardware wird für die Raumregelung Heizen/Kühlen verwendet? | BMS | |
1./2./3.Kreis | Wie viele Raumregler werden mit der BMS Schnittstelle für den 1./2./3.Kreis verwendet? | 1 … 10 |
Note |
---|
WICHTIG |
...
Name | Address | Datapoint Typ | COIL/REG | R/W | Range | Unit | |
---|---|---|---|---|---|---|---|
Min. | Max. | ||||||
Raumadressen 1.Heiz/Kühlkreis | 5065 | uint16 | Register | R/W | 50 | 59 | no |
Raumadressen 2.Heiz/Kühlkreis | 5065 | uint16 | Register | R/W | 60 | 69 | no |
Raumadressen 3.Heiz/Kühlkreis | 5065 | uint16 | Register | R/W | 70 | 79 | no |
Raumtemperatur 50-79 BMS | 11 | uint16 | Register | R/W | 100 | 500 | 0.1 °C |
Raumfeuchte 50-79 BMS | 13 | uint16 | Register | R/W | 200 | 900 | 0.1 % |
Raumsolltemperatur 50-79 BMS | 5081 | uint16 | Register | R/W | 100 | 300 | 0.1 °C |
Raumfreigabe 50-79 BMS | 5164 | uint16 | Register | R/W | 1 | 3 | no |
1: Heizen (Kühlen gesperrt) | |||||||
Zustand Stellventil | 177 | boolean | Coil | R | 0 | 1 | no |
0: geschlossen |
Info |
---|
HINWEIS Beispiel: Zustand Stellventil: |
...
Der Merker 2 (AI Memory flags 2) aus Baustein 2 enthält den aktuellen Wert der Raumadresse die geschrieben werden soll. Damit der richtige Trigger der Raumadresse ausgelöst wird, muss die Raumadresse aus Merker 2 (AI Memory flags 2) verglichen werden. Verglichen wird der Merker 2 (AI Memory flags 2) mit der Konstanten 50 (Constant 50). Ist der Wert gleich wird ein weiterer Merker 50 (AI Memmory flags 50) gesetzt. Der Merker 50 (AI Memory flags 50) wird im Baustein 4 benötgt und löst dort den Trigger aus.
Info |
---|
HINWEIS |
...
Der Baustein 4 wird am Beispiel der Raum-Soll-Temperatur für die Raumadresse 50 (Room-set-temperature 50) erklärt. Zunächst wird die Raum-Soll-Temperatur (Room-set-temperature 50) mit Faktor x10 multipliziert. Dies ist notwendig, da nur Ganzzahlen(*) geschrieben werden. Das Ergebnis wird in einen Analog-Speicher (Analogue memory) geschrieben. Wird nun der Merker 50 (AI Memory flags 50) aus Schritt 3 ausgelöst, wird die im Analog-Speicher (Analogue memory) befindliche Zahl in den Merker RST 50 (AI Memory flags RST 50) geschrieben, der wiederrum gleichzeitig den Aktor 14/5/8 für die Raum-Soll-Temperatur auslöst.
Info |
---|
*HINWEIS |
Info |
---|
HINWEIS |
...
Parameter | Einstellung | Einstellwert |
---|---|---|
Flexeingang | Wird der Digitaleingang ID1 + ID2 verwendet? WEinstellung welche für die Aktivierung der NWPM Touch-Erweiterung vorgenommen werden muss. | Smart Grid |
Info |
---|
HINWEIS* |
...
Color | Description | Detail |
---|---|---|
rot | In diesem Zustand läuft die Wärmepumpe im abgesenkten Betrieb für die Raumheizung, Warmwasser- und Schwimmbadbereitung. |
|
gelb | In diesem Zustand läuft die Wärmepumpe im eingestellten Normalbetrieb. | |
grün | In diesem Zustand läuft die Wärmepumpe im verstärkten Betrieb für die Raumheizung, Warmwasser- und Schwimmbadbereitung. Bei regenerativen Anlagen wird die Wärmepumpe nicht gesperrt, die Wärmepumpe erhält in diesem Zustand Priorität. Der regenerative Speicher wird in der Zeit nicht entladen |
|
dunkelgrün | In diesem Zustand läuft die Wärmepumpe in die Leistungsstufe 3 versetzt. Bedeutet es wird die Wärmepumpe als auch die elektrische Wärmeerzeuger (elektrischer Tauchheizkörper, elektrische Flanschheizung) im verstärkten Betrieb für die Raumheizung, Warmwasser- und Schwimmbadbereitung angefordert. |
|
Info |
---|
*HINWEIS |
...
Die Aktivierung erfolgt über das Register Smar Grid. Dabei können 5 verschiedene Werte geschrieben werden. Bei dem Wert “0” wird die Ausführung der Funktion an den Hardwareeingängen am Wärmepumpenmanager erwartet.
Info |
---|
HINWEIS |
...
Die Aktivierung erfolgt über das Register Sperre Extern. Dabei können 3 verschiedene Werte geschrieben werden. Bei dem Wert “0” wird die Ausführung der Funktion an den Hardwareeingängen am Wärmepumpenmanager erwartet.
Info |
---|
HINWEIS |
...