Address | Datapoint Typ | COIL/REG | R/W | Unit | Name | WPM-Software |
Address | Datapoint Typ | COIL/REG | R/W | Unit | ||
Name | WPM-Software J/L/M | WPM-Software H | ||||
---|---|---|---|---|---|---|
Außentemperatur (R1) | 1 | 27 | int16 | Register | R | 0.1 °C |
Temperatur Ruecklauf (R2) | 2 | 29 | int16 | Register | R | 0.1 °C |
Temperatur Rücklaufsoll | 53 | 28 | int16 | Register | R | 0.1 °C |
Temperatur Warmwasser (R3) | 3 | 30 | int16 | Register | R | 0.1 °C |
Temperatur Warmwassersoll | 58 | 40 | int16 | Register | R | 0.1 °C |
Temperatur Vorlauf (R9) | 5 | 31 | int16 | Register | R | 0.1 °C |
Temperatur Wärmequelleneintritt (R24)* | 6 | - | int16 | Register | R | 0.1 °C |
Temperatur Wärmequellenaustritt (R6) | 7 | 41 | int16 | Register | R | 0.1 °C |
Solltemperatur 2.Heizkreis | 54 | 32 | int16 | Register | R | 0.1 °C |
Temperatur 2.Heizkreis (R5) | 9 | 33 | int16 | Register | R | 0.1 °C |
Solltemperatur 3.Heizkreis | 55 | 34 | int16 | Register | R | 0.1 °C |
Temperatur 3.Heizkreis (R13) | 10 | 35 | int16 | Register | R | 0.1 °C |
Raumtemperatur 1 / RT-RTH Econ | 11 | 36 | int16 | Register | R | 0.1 °C |
Raumtemperatur 2 | 12 | 38 | int16 | Register | R | 0.1 °C |
Raumfeuchte 1 / RT-RTH Econ | 13 | 37 | int16 | Register | R | 0.1 r.F. |
Raumfeuchte 2 | 14 | 39 | int16 | Register | R | 0.1 r.F. |
Passiv Kühlen | ||||||
Vorlauftemperatur (R11) | 19 | 42 | int16 | Register | R | 0.1 °C |
Rücklauftemperatur (R4) | 20 | 43 | int16 | Register | R | 0.1 °C |
Passiv/Aktiv Kühlen | ||||||
Rücklauftemp. gem. Primärkreis (R24) | 21 | - | int16 | Register | R | 0.1 °C |
Solar | ||||||
Kollektorfühler (R23) | 10 | - | int16 | Register | R | 0.1 °C |
Solarspeicher (R22) | 23 | - | int16 | Register | R | 0.1 °C |
Lüftung | ||||||
Außenlufttemperatur | 120 | - | int16 | Register | R | 0.1 °C |
Zulufttemperatur | 121 | - | int16 | Register | R | 0.1 °C |
Ablufttemperatur | 122 | - | int16 | Register | R | 0.1 °C |
Fortlufttemperatur | 123 | - | int16 | Register | R | 0.1 °C |
Drehzahl Zuluftventilator | 125 | - | int16 | Register | R | 1/min |
Drehzahl Abluftventilator | 126 | - | int16 | Register | R | 1/min |
Info |
---|
*HINWEIS |
6.4 Auswahl Zeitfunktionen
Ein Zugriff auf die Zeitfunktionen für z.B. Sperren, Absenk-/ Anhebwerte oder Zeiten erfolgt über das Umschalten der Adresse 5065.
Info |
---|
HINWEIS |
6.4.1 Absenkung/Anhebung
...
Address
...
Datapoint Typ
...
COIL/REG
...
R/W
...
Range
...
Unit
...
Name
...
Min
...
Max
...
1.Heizkreis
...
Absenkung
...
5065
...
uint16
...
Register
...
R/W
...
1
...
1
...
Anhebung
...
5065
...
uint16
...
Register
...
R/W
...
2
...
2
...
2.Heizkreis
...
Absenkung
...
5065
...
uint16
...
Register
...
R/W
...
3
...
3
...
Anhebung
...
5065
...
uint16
...
Register
...
R/W
...
4
...
4
...
3.Heizkreis
...
Absenkung
...
5065
...
uint16
...
Register
...
R/W
...
5
...
5
...
Anhebung
...
5065
...
uint16
...
Register
...
R/W
...
6
...
6
...
Zeitfunktion
...
Start Stunde 1
...
5066
...
uint16
...
Register
...
R/W
...
0
...
23
...
hour
...
Start Minute 1
...
5067
...
uint16
...
Register
...
R/W
...
0
...
59
...
min
...
Ende Stunde 1
...
5068
...
uint16
...
Register
...
R/W
...
0
...
23
...
hour
...
Ende Minute 1
...
5069
...
uint16
...
Register
...
R/W
...
0
...
59
...
min
...
Start Stunde 2
...
5070
...
uint16
...
Register
...
R/W
...
0
...
23
...
hour
...
Start Minute 2
...
5071
...
uint16
...
Register
...
R/W
...
0
...
59
...
min
...
Ende Stunde 2
...
5072
...
uint16
...
Register
...
R/W
...
0
...
23
...
hour
...
Ende Minute 2
...
5073
...
uint16
...
Register
...
R/W
...
0
...
59
...
min
...
Sonntag
...
5074
...
uint16
...
Register
...
R/W
...
0
...
3
...
Montag
...
5075
...
uint16
...
Register
...
R/W
...
0
...
3
...
Dienstag
...
5076
...
uint16
...
Register
...
R/W
...
0
...
3
...
Mittwoch
...
5077
...
uint16
...
Register
...
R/W
...
0
...
3
...
Donnerstag
...
5078
...
uint16
...
Register
...
R/W
...
0
...
3
...
Freitag
...
5079
...
uint16
...
Register
...
R/W
...
0
...
3
...
Samstag
...
5080
...
uint16
...
Register
...
R/W
...
0
...
3
...
0: Ja
1: Nein
2: Zeit 1
3: Zeit 2
...
Absenk- / Anhebwert
...
5081
...
uint16
...
Register
...
R/W
...
0
...
19
...
K
...
Aktiv Zeit 1
...
125
...
Boolean
...
Coil
...
R
...
0
...
1
...
no
...
Aktiv Zeit 2
...
126
...
Boolean
...
Coil
...
R
...
0
...
1
...
no
...
6.8 Zeitabgleich
Über den Zeitabgleich ist es möglich das aktuelle Datum und die Uhrzeit über die Schnittstelle zu schreiben. Damit die Änderung vom Wärmepumpenmanager übernommen wird, muss nach dem Schreiben der Zeit sofort noch der Wert 1 auf das zugehörige "set Register" geschrieben werden. Erst dann wird die Änderung übernommen. Der Wert des "set Registers" setzt sich nach dem Schreiben automatisch wieder auf den Wert 0 zurück.
Address | Datapoint Typ | COIL/REG | R/W | Range | Unit | ||
---|---|---|---|---|---|---|---|
Name | Min. | Max. | |||||
Stunde | 5006 | uint16 | Register | R/W | 0 | 23 | hour |
set Stunde | 102 | boolean | Coil | W | |||
Minute | 5007 | uint16 | Register | R/W | 0 | 59 | min |
set Minute | 103 | boolean | Coil | W | |||
Monat | 5008 | uint16 | Register | R/W | 1 | 12 | month |
set Monat | 105 | boolean | Coil | W | |||
Wochentag | 5009 | uint16 | Register | R/W | 1 | 7 | |
1:Montag | |||||||
set Wochentag | 107 | boolean | Coil | W | |||
Tag | 5010 | uint16 | Register | R/W | 1 | 31 | day |
set Tag | 104 | boolean | Coil | W | |||
Jahr | 5011 | uint16 | Register | R/W | 0 | 99 | year |
set Jahr | 106 | boolean | Coil | W |
Info |
---|
*HINWEIS |
...
Parameter | Einstellung | Einstellwert | |
---|---|---|---|
1./2./3.Kreis | |||
1./2./3.Kreis | Welche Regelungsmöglichkeit soll für den 1./2./3.Kreis genutzt werden? | Raumtemperatur | |
1./2./3.Kreis | Welche Hardware wird für die Raumregelung Heizen/Kühlen verwendet? | BMS | |
1./2./3.Kreis | Wie viele Raumregler werden mit der BMS Schnittstelle für den 1./2./3.Kreis verwendet? | 1 … 10 |
Note |
---|
WICHTIG |
...
Name | Address | Datapoint Typ | COIL/REG | R/W | Range | Unit | |
---|---|---|---|---|---|---|---|
Min. | Max. | ||||||
Raumadressen 1.Heiz/Kühlkreis | 5065 | uint16 | Register | R/W | 50 | 59 | no |
Raumadressen 2.Heiz/Kühlkreis | 5065 | uint16 | Register | R/W | 60 | 69 | no |
Raumadressen 3.Heiz/Kühlkreis | 5065 | uint16 | Register | R/W | 70 | 79 | no |
Raumtemperatur 50-79 BMS | 11 | uint16 | Register | R/W | 100 | 500 | 0.1 °C |
Raumfeuchte 50-79 BMS | 13 | uint16 | Register | R/W | 200 | 900 | 0.1 % |
Raumsolltemperatur 50-79 BMS | 5081 | uint16 | Register | R/W | 100 | 300 | 0.1 °C |
Raumfreigabe 50-79 BMS | 5164 | uint16 | Register | R/W | 1 | 3 | no |
1: Heizen (Kühlen gesperrt) | |||||||
Zustand Stellventil | 177 | boolean | Coil | R | 0 | 1 | no |
0: geschlossen |
Info |
---|
HINWEIS Beispiel: Zustand Stellventil: |
...
Der Merker 2 (AI Memory flags 2) aus Baustein 2 enthält den aktuellen Wert der Raumadresse die geschrieben werden soll. Damit der richtige Trigger der Raumadresse ausgelöst wird, muss die Raumadresse aus Merker 2 (AI Memory flags 2) verglichen werden. Verglichen wird der Merker 2 (AI Memory flags 2) mit der Konstanten 50 (Constant 50). Ist der Wert gleich wird ein weiterer Merker 50 (AI Memmory flags 50) gesetzt. Der Merker 50 (AI Memory flags 50) wird im Baustein 4 benötgt und löst dort den Trigger aus.
Info |
---|
HINWEIS |
...
Der Baustein 4 wird am Beispiel der Raum-Soll-Temperatur für die Raumadresse 50 (Room-set-temperature 50) erklärt. Zunächst wird die Raum-Soll-Temperatur (Room-set-temperature 50) mit Faktor x10 multipliziert. Dies ist notwendig, da nur Ganzzahlen(*) geschrieben werden. Das Ergebnis wird in einen Analog-Speicher (Analogue memory) geschrieben. Wird nun der Merker 50 (AI Memory flags 50) aus Schritt 3 ausgelöst, wird die im Analog-Speicher (Analogue memory) befindliche Zahl in den Merker RST 50 (AI Memory flags RST 50) geschrieben, der wiederrum gleichzeitig den Aktor 14/5/8 für die Raum-Soll-Temperatur auslöst.
Info |
---|
*HINWEIS |
Info |
---|
HINWEIS |
...
Parameter | Einstellung | Einstellwert |
---|---|---|
Flexeingang | Wird der Digitaleingang ID1 + ID2 verwendet? WEinstellung welche für die Aktivierung der NWPM Touch-Erweiterung vorgenommen werden muss. | Smart Grid |
Info |
---|
HINWEIS* |
...
Color | Description | Detail |
---|---|---|
rot | In diesem Zustand läuft die Wärmepumpe im abgesenkten Betrieb für die Raumheizung, Warmwasser- und Schwimmbadbereitung. |
|
gelb | In diesem Zustand läuft die Wärmepumpe im eingestellten Normalbetrieb. | |
grün | In diesem Zustand läuft die Wärmepumpe im verstärkten Betrieb für die Raumheizung, Warmwasser- und Schwimmbadbereitung. Bei regenerativen Anlagen wird die Wärmepumpe nicht gesperrt, die Wärmepumpe erhält in diesem Zustand Priorität. Der regenerative Speicher wird in der Zeit nicht entladen |
|
dunkelgrün | In diesem Zustand läuft die Wärmepumpe in die Leistungsstufe 3 versetzt. Bedeutet es wird die Wärmepumpe als auch die elektrische Wärmeerzeuger (elektrischer Tauchheizkörper, elektrische Flanschheizung) im verstärkten Betrieb für die Raumheizung, Warmwasser- und Schwimmbadbereitung angefordert. |
|
Info |
---|
*HINWEIS |
...
Die Aktivierung erfolgt über das Register Smar Grid. Dabei können 5 verschiedene Werte geschrieben werden. Bei dem Wert “0” wird die Ausführung der Funktion an den Hardwareeingängen am Wärmepumpenmanager erwartet.
Info |
---|
HINWEIS |
...
Die Aktivierung erfolgt über das Register Sperre Extern. Dabei können 3 verschiedene Werte geschrieben werden. Bei dem Wert “0” wird die Ausführung der Funktion an den Hardwareeingängen am Wärmepumpenmanager erwartet.
Info |
---|
HINWEIS |
...